Electrical installation
5.2
Electrical installation
5.2.1
EMC-compliant wiring
In typical systems, standard shielding is sufficient for Ethernet cables.
However, in environments with a very high level of interference, EMC resistance can be
improved by additionally earthing the cable shield on both sides.
For this observe the following notes:
1. The distance between the additional earthing and the Ethernet plug depends on the
module slot and is as follows:
– Approx. 10 cm for the upper slot (MXI1)
– Approx. 20 cm for the lower slot (MXI2)
2. Measure the appropriate distance along the cable and, starting from this point, remove
2 cm of the cable's plastic sheath.
3. Fasten the cable shield onto the shield sheet of the Servo Drive 9400.
[5-3]
EMC-compliant wiring
Documentation for the standard device, control system, system/machine
Observe the notes and wiring instructions contained in this documentation.
E94YCXX008
A Fastening on the shield sheet of the Servo Drive
9400
B Outgoing Ethernet cable at X216
C Incoming Ethernet cable at X215
D Communication module in slot MXI1 of the
Servo Drive 9400