Commissioning

DIP switch settings

7

EDK94AYCIB DE/EN/FR/ES/IT 1.0

49

l

H1inbet−ueb−rate einstellen

Setting the number of parameter data words (PCP)

ƒ You can use switches 5 and 6 or the code C13892 / C14892 to set the number of

parameter data words.

ƒ 0, 1, 2 or 4 parameter data words can be used.
ƒ The current setting is shown in C13860/1 / C14860/1.

)

Note!

The total number of data words (PD + PCP) must be between 1 and 10.
Impermissible settings are signalled by the "BE" LED (flashes

^ 51

) red).

The communication module then works internally with the following values:

ƒ

PD = 2 (words)

ƒ

PCP = 1 (word)

DIP switch

Number of PCP

Switch

Max. number of

PD

ID code

[hex]

5

6

12345678

ON

OFF

0

OFF

OFF

10

0x03

1

OFF

ON

9

0xE3

2

ON

OFF

8

0xE0

4

ON

ON

6

0xE1