Commissioning

DIP switch settings

EDK94AYCIB DE/EN/FR/ES/IT 1.0

48

l

H1inbet−ueb−rate einstellen

Setting the number of process data words (PD)

ƒ You can use switches 1 to 4 or the code C13893 / C14893 to set the number of

process data words.

ƒ 0 to 10 process data words can be used.
ƒ The current setting is shown in C13860/2 / C14860/2.

)

Note!

The total number of data words (PD + PCP) must be between 1 and 10.
Impermissible settings are signalled by the "BE" LED (flashes

^ 51

) red.

The communication module then works internally with the following values:

ƒ

PD = 2 (words)

ƒ

PCP = 1 (word)

DIP switch

Number of PD

Switch

Max. number

of PCP

1

2

3

4

12345678

ON

OFF

0

OFF

OFF

OFF

OFF

4

1

OFF

OFF

OFF

ON

2

OFF

OFF

ON

OFF

3

OFF

OFF

ON

ON

4

OFF

ON

OFF

OFF

5

OFF

ON

OFF

ON

6

OFF

ON

ON

OFF

7

OFF

ON

ON

ON

2

8

ON

OFF

OFF

OFF

9

ON

OFF

OFF

ON

1

10

ON

OFF

ON

OFF

0