beautypg.com

Lenze E94AYCIB User Manual

Page 47

background image

Commissioning

DIP switch settings

7

EDK94AYCIB DE/EN/FR/ES/IT 1.0

47

l

H1inbet−ueb−rate einstellen

)

Note!

Switch off the voltage supply of the communication module and then on
again in order to activate changed settings.

You can also carry out the settings by means of codes:

ƒ

All DIP switches = "OFF" (Lenze setting):
When you switch the power on, the configuration determined by the
codes C13892/C14892, C13893/C14893 and C13894/C14894 becomes
active.

ƒ

At least one DIP switch = "ON":
When the power is switched on, the values determined by the switch
settings are adopted.

The total number of data words (PD + PCP) must not exceed 10.