Commissioning
WORD0 - Controller status in C0135 format
Bit
h86 / h96 setting = 2
WORD0 - Controller status in C0135 format
Bit
h86 / h96 setting = 3
0
JOG1, JOG2, JOG3
0 = C46 active
1 = JOG1 (C37) active
2 = JOG2 (C38) active
3 = JOG3 (C39) active
0
JOG1, JOG2, JOG3
0 = C46 active
1 = JOG1 (C37) active
2 = JOG2 (C38) active
3 = JOG3 (C39) active
1
1
2
Direction of rotation
0 = CW (forward)
1 = CCW (reverse)
2
Direction of rotation
0 = CW (forward)
1 = CCW (reverse)
3
Quick stop
0 = Quick stop not active
1 = Quick stop active
3
Quick stop
0 = Quick stop not active
1 = Quick stop active
4
reserved
4
reserved
5
reserved
5
reserved
6
reserved
6
reserved
7
reserved
7
reserved
8
reserved
8
reserved
9
Controller inhibit
0 = No controller inhibit
1 = Controller inhibit
9
Controller inhibit
0 = No controller inhibit
1 = Controller inhibit
10
reserved
10
reserved
11
TRIP reset
0 = No TRIP reset
1 = TRIP reset
11
TRIP reset
0 = No TRIP reset
1 = TRIP reset
12
reserved
12
reserved
13
reserved
13
reserved
14
DC brake
0 = DC brake not active
1 = DC brake active
14
DC brake
0 = DC brake not active
1 = DC brake active
15
reserved
15
reserved
WORD1
•
Signed frequency setpoint [Hz]
•
Scaling = frequency setpoint [Hz] x 50
•
Example 1: CW at 34.5 Hz = 34.5 x 50 = 1725 =
0x06BD
•
Example 2: CCW at 44.5 Hz = - (44.5 x 50) = -
2225 = 0xF74F
WORD1
•
Unsigned frequency setpoint [Hz]
•
Scaling = frequency setpoint [Hz] x 10
•
Example: CW at 34.5 Hz = 34.5 x 10 = 345 =
0x0159
•
Direction is indicated by bit 2 in WORD0
WORD2
reserved
WORD3
reserved