Installation, 3 connection diagram, Danger – Lenze SMD 0-25kW-4-0kW Basic I/O User Manual
Page 12
10
Lenze 13466185 EDBSW03 v5
Installation
3.2.3
Connection diagram
PE PE
U V W
PE
L1 L2/N
PE
PE
M
3~
7
28 E1 E2 E3
PE
N
L3
L2
L1
1/N/PE 180 V - 0 % … 264 V + 0 %
48 Hz … 62 Hz
-
+
PE
L1
L2/N
PE
N
L3
L2
L1
2/PE 180V - 0% … 264V + 0 %
48 Hz … 62 Hz
0.5 Nm / 4.5 lb-in
6 mm / 0.24 in
PES
PES
PES
PES
0.2 Nm / 2 lb-in
6 mm / 0.24 in
< 1 mm2 / AWG 26…16
_
+12 VDC - 0 %
…
+30 VDC + 0 %
L1
L2
PE
N
L3
L2
L1
3/PE 180V - 0% … 264V + 0 %
48 Hz … 62 Hz
L3
PE
20
28
E1 E2 E3 7 K14 K12
CAN_H
+12V
CO
M
CAN_L
CAN_GND
V0001
DANGER!
• Hazard of electrical shock! Circuit potentials are up to 240VAC above earth ground.
Capacitors retain charge after power is removed. Disconnect power and wait until
the voltage between B+ and B- is 0VDC before servicing the drive.
• Do not connect mains power to the output terminals (U, V, W)! Severe damage to
the drive will result.
• Do not cycle mains power more than once every three minutes. Damage to the
drive will result.