Commissioning – Lenze SMD 0-25kW-4-0kW Basic I/O User Manual
Page 19

Lenze 13466185 EDBSW03 v5
17
Commissioning
Code
Possible Settings
IMPORTANT
No.
Name
Lenze
Selection
c42
Start condition
(with mains on)
1
0 Start after LOW-HIGH change at
terminal 28
See also c70
1 Auto start if terminal 28 = HIGH
WARNING!
Automatic starting/restarting may cause damage to equipment and/or injury to
personnel! Automatic starting/restarting should only be used on equipment that is
inaccessible to personnel.
c60
Mode selection
for c61
0
0 Monitoring only
c60 = 1 allows the keys
to adjust
speed setpoint (c40) while monitoring
c61
1 Monitoring and editing
c61
Present status/error
status/error message
•
Display
• Refer to Section 5 for explanation of
status and error messages
c62
Last error
error message
c63
Last error but one
c70
Configuration TRIP
reset (error reset)
0
0 TRIP reset after LOW-HIGH
change at terminal 28, mains
switching, or after LOW-HIGH
change at digital input “TRIP reset”
1 Auto-TRIP reset
•
Auto-TRIP reset after the time set in
c71
•
More than 8 errors in 10 minutes will
trigger
rSt
fault
WARNING!
Automatic starting/restarting may cause damage to equipment and/or injury to
personnel! Automatic starting/restarting should only be used on equipment that is
inaccessible to personnel.
c71
Auto-TRIP reset
delay
0.0 0.0
{s}
60.0 See c70
c78
Operating time
counter
Display
Total time in status “Start”
0...999 h: format xxx
1000...9999 h: format x.xx (x1000)
10000...99999 h: format xx.x (x1000)
c79
Mains connection
time counter
Display
Total time of mains = on
CANopen / System bus parameters
h42
Guard time
0
0
{ms}
65535
•
h42 x h43 = node life time
•
If RTR frame with ID = 0x700 + Node
ID (h50) is not received during the
node life time, the controller will react
according to h44
•
If heart beat message is enabled, the
guard function is disabled
•
h44 is only active when C01 = 3 and
h42 x h43 > 0
h43
Life time factor
0
0 255
h44
Guard time event
reaction
0
0 Not active
1 Inhibit
2 Quick stop
3 Trip fault
FC3
h45
Error behavior
1
0 transition to pre-operational
(only if current state is operational)
Specifies action taken by the drive when
it encounters a communication error
(ex. Node guarding event or Bus Off)
1 No state change
2 transition to stopped
h46
Message monitoring
time
0
0
{ms}
65535
•
h46 and h47 can be used to monitor
all valid messages (e.g. SDO, SYNC,
PDO...).
•
h46 = 0 or h47 = 0 disables message
monitoring function
•
h47 is only active when C01 = 3
h47
Message monitoring
time out reaction
0
0 Not active
1 Inhibit
2 Quick stop
3 Trip fault
FC3