(1)
These parameters take effect only after power-up, h58 reset, “NMT reset node”, or “NMT reset communication services”
Code
Possible Settings
IMPORTANT
No.
Name
Lenze
Selection
h53
(1)
Parameter channel
2
(SDO#2 support for
Lenze Systembus)
0
0 Enable: Node ID range (1...63)
with default COB ID for SYNC,
RPDO and TPDO
•
h53 = 0, 1: CAN address 1...63; used
for SDO1. 64...127 used for SDO2.
•
SDO#1 COB ID = 1536 + Node ID
•
SDO#2 COB ID = 1600 + Node ID (if
enabled)
1 Enable: Node ID range (1...63)
with programmable COB ID using
h54, h60, h70, h80, h90
2 Disable: Node ID range (1...127)
with default COB ID for SYNC,
RPDO, and TPDO
3 Disable: Node ID range (1...127)
with programmable COB ID using
h54, h60, h70, h80, h90
h54
(1)
SYNC COB ID
128 0 2047 Note: Controller does not generate
SYNC object
h55
(1)
Boot up time
3000 0
{ms}
65535 Controller sends “NMT start all nodes”
message after this delay (active only
when h52 = 2)
h56
Heartbeat time
2000 0
{ms}
65535
•
Producer heartbeat time
•
h56 = 0 disables heartbeat
transmission
h58
Reset CAN node
0
0 No action
On transition from 0 to 1, re-initializes
CAN controller and activates changes
made to parameters marked with
(1)
1 Reset CAN communication
WARNING!
CAN re-initialization may activate new RPDO configurations, which can result in
changes to present controller state, including starting.
h59
CANopen status
0 Not initialized
•
Read-only
•
Note: RPDOs and TPDOs are only
active in operational state (h59 = 5)
1 Initializing
2 Stopped
3 Pre-operational
4 reserved
5 Operational
RPDO#1 configuration parameters
h60
(1)
RPDO#1 COB ID
513 0 2047 If h53 = 0, 2: Setting will change to 512
+ Node ID during power-up or h58 reset.
h61
(1)
RPDO#1 enable/
disable
1
0 Disable
1 Enable
h62
RPDO#1
transmission type
255 0 255
•
h62 = 0...240: transfer on every
SYNC received.
•
h62 = 254, 255: immediate transfer
h64
RPDO#1 event
monitoring timer
0
0
{ms}
65535 h64 = 0: monitoring disabled
h65
RPDO#1 time out
reaction
0
0 Not active
Only active when C01 = 3
1 Inhibit
2 Quick stop
3 Trip fault FC3