Commissioning – Lenze SMD 0-25kW-4-0kW Basic I/O User Manual
Page 23

Lenze 13466185 EDBSW03 v5
21
Commissioning
(1)
These parameters take effect only after power-up, h58 reset, “NMT reset node”, or “NMT reset communication services”
Code
Possible Settings
IMPORTANT
No.
Name
Lenze
Selection
TPDO#1 configuration parameters
h80
(1)
TPDO#1 COB ID
385 0 2047 If h53 = 0, 2: Setting will change to
384 + Node ID during power-up or h58
reset.
h81
(1)
TPDO#1 enable/
disable
1
0 Disable
1 Enable (no RTR)
2 Enable (with RTR)
Enable individual polling of TPDO#1
h82
TPDO#1
transmission type
255 0 255
•
h82 = 0...240: Transmit TPDO#1 after
every n
th
SYNC received + Event +
RTR (if enabled)
•
h82 = 253: Event + RTR (if enabled)
•
h82 = 254: COS triggered (WORD0 of
TPDO#1) + Event + RTR (if enabled)
•
h82 = 255: Event + RTR (if enabled)
h83
(1)
TPDO#1 inhibit time
50
0
{0.1 ms}
65535 Sets minimum time between TPDO#1
transmissions (h83 = 50 = 5.0 ms)
h84
TPDO#1 event
timer
0
0
{ms}
65535
•
Sets the fixed interval for TPDO#1
transmission
•
h84 = 0: disables event timer
h86
(1)
TPDO#1 mapping
(see TPDO
mapping details)
0
0 C0150 + C50 signed
C50 scaling: + 50 = + 1.0 Hz
1 C0150 + C50 unsigned
C50 scaling: 10 = 1.0 Hz
2 Controller status in C0135 format +
frequency setpoint signed
Can be used to control other controllers
(see example in section 4.5)
3 Controller status in C0135 format +
frequency setpoint unsigned
4 402 Device profile: Statusword
0x6041
5 402 Device profile: Statusword
0x6041 + vl control effort 0x6044
•
vl control effort units = signed RPM
•
RPM calculation based on C87 and C89
6 C0150 + C50 signed and scaled +
digital input
C50 scaling: +/- 16384 = C11
h87
TPDO#1 WORD0
bit mask
65535
0
65535
•
COS (change of state) bit mask
applied to WORD0 of TPDO selected
by h86.
•
h87 = 65535: activates all bits of
WORD0 for COS triggering
•
h87 = 0: disables COS triggering
h89
TPDO#1 status
0 255
•
Read-only
•
Number of transmitted TPDO#1
messages
•
Above 255, starts over at 0