Commissioning – Lenze SMD 0-25kW-4-0kW Basic I/O User Manual
Page 18

16
Lenze 13466185 EDBSW03 v5
Commissioning
Code
Possible Settings
IMPORTANT
No.
Name
Lenze
Selection
C37
Fixed setpoint 1
(JOG 1)
20.0 0.0 {Hz} 240
C38
Fixed setpoint 2
(JOG 2)
30.0 0.0 {Hz} 240
C39
Fixed setpoint 3
(JOG 3)
40.0 0.0 {Hz} 240
C46
Frequency setpoint
0.0 {Hz} 240 Display: Setpoint via CANopen or
function UP/DOWN
C50
Output frequency
0.0 {Hz} 240 Display
C53
DC bus voltage
0.0 {%} 255 Display
C54
Motor current
0.0 {%} 255 Display
C87
Motor rated speed
1390 300 {RPM} 32000 Set to motor nameplate speed
C89
Motor rated
frequency
50
10 {Hz} 1000 Set to motor nameplate frequency
C94
User password
0
0 999
Changing from “0” (no password), value
will start at 763
When set to a value other than 0,
must enter password at C00 to access
parameters
C99
Software version
Display, format: x.yz
c06
Holding time -
automatic DC
injection brake
(Auto-DCB)
0.0 0.0
{s}
999
0.0 = not active
999 = continuous brake
•
Automatic motor braking below 0.1 Hz
by means of motor DC current for the
entire holding time (afterwards: U, V,
W inhibited)
•
Confirm motor suitability for use with
DC braking
c20
I
2
t switch-off
(thermal motor
monitoring)
100 30 {%} 100
100% = smd rated output current
• Triggers
0C6
fault when motor current
exceeds c20 for too long
• Correct setting = (motor nameplate
current) / (smd output current rating) X
100%
• Example: motor = 6.4 amps and smd
= 7.0 amps; correct setting = 91%
(6.4 / 7.0 = 0.91 x 100% = 91%)
NOTE
Do not set above the rated motor current as listed on the motor dataplate. The
motor thermal overload function is UL approved as a motor protection device. If
line power is cycled, the motor thermal state is reset to cold state. Cycling power
after an overload fault may result in reducing the motor life.
c21
Motor Overload
Type
00
00 Speed Compensation
Reduces the allowable continuous
current when operating below
30Hz.
Ir
100%
60%
30 f
1
0
Ir: rated current (%), f: motor frequency (Hz)
01 No Speed Compensation
Example: Motor is cooled by forced
ventilation as apposed to shaft
mounted, self cooling fans.
c40
Frequency setpoint
via keys
0.0 0.0
{Hz}
240 Only active if C01 = 0, 1