4 terminal box, Terminal box, Electrical installation – Lenze MDFQA Operating Instructions User Manual
Page 32

Electrical installation
Terminal box
Feedback system
EN
32
Lenze ¯ BA 33.0006 ¯ 3.0
6.4
Terminal box
Terminal box with knock out
Terminal box with screwed connections
MT−terminal box−001.iso
MT−terminal−box−002.iso
The openings in the terminal box are cast closed
and can be opened by the customer as required.
)
Note!
Open the holes on the underside of the knock out terminal box when the
cover is closed.
Cable glands and terminal studs for the power terminal box
Motor type /
motor size
Power connection
Screwed connections
Terminal
Terminal board
Cable
cross−section
[mm
2
]
Stripping length
[mm]
Tightening
torque [Nm]
Threaded
bolt
Tightening
torque [Nm]
MCA
10, 13,
14, 17
1 x M20 x 1.5 + 1 x M16 x 1.5
0.08 ... 2.5
10 ... 11
2)
−−−−−
−−−−−
19, 21
1 x M32 x 1.5 + 1 x M25 x 1.5
0.2 ... 10
10 ... 11
2)
−−−−−
−−−−−
20
2 x M20 + 2 x M 25 + 2 x M32
2.5 ... 16
18 ... 20
2)
−−−−−
−−−−−
22
1 x M40x1.5 + 1 x M50x1.5 +
1 x M20x1.5 + 1 x M16x1.5
10 ... 35
18
3,2
−−−−−
−−−−−
26
1 x M50 x 1.5 + 1 x M63 x 1.5 +
1 x M20 x 1.5 + 1 x M16 x 1.5
−−−−−
M12
15.5
MQA
20
2 x M20 + 2 x M 25 + 2 x M32
2.5 ... 16
18 ... 20
2)
−−−−−
−−−−−
22
1 x M40x1.5 + 1 x M50x1.5 +
1 x M20x1.5 + 1 x M16x1.5
10 ... 35
18
3.2
−−−−−
−−−−−
26
1 x M50 x 1.5 + 1 x M63 x 1.5 +
1 x M20 x 1.5 + 1 x M16 x 1.5
−−−−−
M12
15.5
MCS
09, 12,
14D,
14H,
14L15,
14P14,
19F15,
19J15
2 x M20 + 2 x M25 + 2 x M32
0.08 ... 2.5
1)
10 ... 11
2)
−−−−−
−−−−−
14L32,
14P32,
19F13,
19J30,
19P
0.2 ... 10
10 ... 11
2)
−−−−−
−−−−−
MDFQA
160
2 x M63 x 1.5 + 1 x M16 x 1.5
M12
15.5
MD
LKS 056,
071
1 x M20 x 1.5 + 1 x M16 x 1.5
0.08 ... 2.5
10 ... 11
2)
−−−−−
−−−−−
Tab. 1
Cable glands and connecting terminals
1) 4 mm
2
without wire end ferrule
2) Spring terminal