Cabling – ERICO TSG Series Surge Reduction Filters (TSG-RSF) User Manual
Page 16

www.erico.com
16
Cabling
Table 2. Termination details for TSG-SRFs.
Table 3. Recommended tightening torques.
Bolt/Screw
Recommended Torque
Location
M6
4.2 Nm
(3.1 ft.lbs)
TSG-SRF140, 163, 340, 363 input terminals
M6
3.5 Nm
(2.6 ft.lbs)
all locations except as above
M8
14.0 Nm (10.3 ft.lbs)
TSG-SRF1125, 3125 phase input terminals
M8
8.5 Nm
(6.3 ft.lbs)
all locations except as above
M10
44.0 Nm (32.0 ft.lbs)
TSG-SRF3200, 3400, 3630 phase input terminals
M10
17.0 Nm (12.5 ft.lbs)
all locations except as above
Filter Rating
Maximum Accepted Cable Size
Phases(s)
Neutral
Earth
Termination Size
Termination Size
Termination Size
Method
Method
Method
Single Phase
40A
Input
Screw Clamp
50 mm
2
Screw Clamp
50 mm
2
Output
Screw Clamp
35 mm
2
Screw Clamp
35 mm
2
Stud*
8 mm
63A
Input
Screw Clamp
50 mm
2
Screw Clamp
50 mm
2
Stud*
8 mm
Output
Screw Clamp
35 mm
2
Screw Clamp
35 mm
2
125A
Input
Stud
8 mm
Stud
8 mm
Stud*
8 mm
Output
Stud
8 mm
Stud
8 mm
Stud*
8 mm
Three-Phase
40A
Input
Screw Clamp
50 mm
2
Screw Clamp
50 mm
2
Stud*
8 mm
Output
Screw Clamp
35 mm
2
Screw Clamp
35 mm
2
63A
Input
Screw Clamp
50 mm
2
Screw Clamp
50 mm
2
Stud*
8 mm
Output
Screw Clamp
35 mm
2
Screw Clamp
35 mm
2
125A
Input
Bolt
8 mm
Bolt
8 mm
Stud
8 mm
Output
Bolt
8 mm
Bolt
8 mm
Stud
8 mm
200A
Input
Bolt
10 mm
Bolt
10 mm
Stud
8 mm
Output
Bolt
10 mm
Bolt
10 mm
Stud
8 mm
400A
Input
Bolt
10 mm
Bolt
10 mm
Stud
8 mm
Output
Bolt
10 mm
Bolt
10 mm
Stud
8 mm
630A
Input
6 x Bolt
10 mm
6 x Bolt
10 mm
Stud
8 mm
Output
6 x Bolt
10 mm
6 x Bolt
10 mm
Stud
8 mm
1250A
Input
6 x Bolt
12 mm
6 x Bolt
12 mm
2 x Stud
8 mm
Output
6 x Bolt
12 mm
6 x Bolt
12 mm
2 x Stud
8 mm
2000A
Input
6 x Bolt
12 mm
6 x Bolt
12 mm
2 x Stud
8 mm
Output
6 x Bolt
12 mm
6 x Bolt
12 mm
2 x Stud
8 mm
* Input and output earths on 40 and 63A TSG-SRFs use a common earth stud.
E535IS06ENAS 10/6/06 11:12 AM Page 16