beautypg.com

Cabling – ERICO TSG Series Surge Reduction Filters (TSG-RSF) User Manual

Page 16

background image

www.erico.com

16

Cabling

Table 2. Termination details for TSG-SRFs.

Table 3. Recommended tightening torques.

Bolt/Screw

Recommended Torque

Location

M6

4.2 Nm

(3.1 ft.lbs)

TSG-SRF140, 163, 340, 363 input terminals

M6

3.5 Nm

(2.6 ft.lbs)

all locations except as above

M8

14.0 Nm (10.3 ft.lbs)

TSG-SRF1125, 3125 phase input terminals

M8

8.5 Nm

(6.3 ft.lbs)

all locations except as above

M10

44.0 Nm (32.0 ft.lbs)

TSG-SRF3200, 3400, 3630 phase input terminals

M10

17.0 Nm (12.5 ft.lbs)

all locations except as above

Filter Rating

Maximum Accepted Cable Size

Phases(s)

Neutral

Earth

Termination Size

Termination Size

Termination Size

Method

Method

Method

Single Phase

40A

Input

Screw Clamp

50 mm

2

Screw Clamp

50 mm

2

Output

Screw Clamp

35 mm

2

Screw Clamp

35 mm

2

Stud*

8 mm

63A

Input

Screw Clamp

50 mm

2

Screw Clamp

50 mm

2

Stud*

8 mm

Output

Screw Clamp

35 mm

2

Screw Clamp

35 mm

2

125A

Input

Stud

8 mm

Stud

8 mm

Stud*

8 mm

Output

Stud

8 mm

Stud

8 mm

Stud*

8 mm

Three-Phase

40A

Input

Screw Clamp

50 mm

2

Screw Clamp

50 mm

2

Stud*

8 mm

Output

Screw Clamp

35 mm

2

Screw Clamp

35 mm

2

63A

Input

Screw Clamp

50 mm

2

Screw Clamp

50 mm

2

Stud*

8 mm

Output

Screw Clamp

35 mm

2

Screw Clamp

35 mm

2

125A

Input

Bolt

8 mm

Bolt

8 mm

Stud

8 mm

Output

Bolt

8 mm

Bolt

8 mm

Stud

8 mm

200A

Input

Bolt

10 mm

Bolt

10 mm

Stud

8 mm

Output

Bolt

10 mm

Bolt

10 mm

Stud

8 mm

400A

Input

Bolt

10 mm

Bolt

10 mm

Stud

8 mm

Output

Bolt

10 mm

Bolt

10 mm

Stud

8 mm

630A

Input

6 x Bolt

10 mm

6 x Bolt

10 mm

Stud

8 mm

Output

6 x Bolt

10 mm

6 x Bolt

10 mm

Stud

8 mm

1250A

Input

6 x Bolt

12 mm

6 x Bolt

12 mm

2 x Stud

8 mm

Output

6 x Bolt

12 mm

6 x Bolt

12 mm

2 x Stud

8 mm

2000A

Input

6 x Bolt

12 mm

6 x Bolt

12 mm

2 x Stud

8 mm

Output

6 x Bolt

12 mm

6 x Bolt

12 mm

2 x Stud

8 mm

* Input and output earths on 40 and 63A TSG-SRFs use a common earth stud.