Det-Tronics X3302 Multispectrum IR Flame Detector with HART User Manual
Page 18
16
2.3
95-8613
ConFIgurATIon menu
1) Consecutive
oi Fails
This option allows the operator to select the number of consecutive oi failures
before an oi fault will be generated. Selectable range is 1 to 1000.
2) Temp setpoint
Internal target temperature that the heater will attempt to maintain (in degrees C).
3) heater setpoint
This option allows the operator to select the maximum amount of heater power
allowed, in percent of full power. (0% = heater shut off.)
CALIBrATIon menu
1) Loop test
This test allows the operator to manually set the analog signal output (
4
to
20
mA)
to a fixed user defined value.
2) d/A trim
This function allows adjustment of the
4
to
20
mA span factor.
3) Calibrate
oi
This procedure calibrates the oi test signal for all three IR sensors.
1. Bypass/disable all Alarm outputs connected to the detector.
2. Thoroughly clean the sensor and oi reflector for each of the three sensors.
Check each of the three oi source openings for contaminants and clean as
needed.
3. Cover the detector with the provided cover.
4. Initiate oi Calibration. The detector performs the calibration automatically and
notifies the operator upon completion. The procedure takes approximately two
minutes.
5. Upon completion of oi calibration, remove the cover and return all alarm outputs
to service.
Configuration Menu
1) Consecutive Oi Fails
2) Temp Setpoint
3) Heater Setpoint
Device Setup Menu
1) Configuration Menu
2) Calibration Menu
3) Write protect
4) HART Setup
5) Real Time Clock
X3302 Root Menu
1) Fire (Yes/No)
2) Fault (Yes/No)
3) Device Info Menu
4) Command Menu
5) Device Setup Menu
Calibration Menu
1) Loop test
2) D/A trim
3) Calibrate Oi
Device Setup Menu
1) Configuration Menu
2) Calibration Menu
3) Write protect
4) HART Setup
5) Real Time Clock
X3302 Root Menu
1) Fire (Yes/No)
2) Fault (Yes/No)
3) Device Info Menu
4) Command Menu
5) Device Setup Menu