Det-Tronics X3302 Multispectrum IR Flame Detector with HART User Manual
Page 14

12
2.3
95-8613
oi
menu
1) Left
oi
Percentage of calibrated oi test signal returned by the left sensor. Reading should
be
90
to
100
percent. If reading is below 90 percent, go to “Device Setup”, select
“Calibration”, and perform oi Calibration.
2) middle
oi
Percentage of calibrated oi test signal returned by the middle sensor. Reading
should be
90
to
100
percent. If reading is below 90 percent, go to “Device
Setup”, select “Calibration”, and perform oi Calibration.
3) right
oi
Percentage of calibrated oi test signal returned by the right sensor. Reading
should be
90
to
100
percent. If reading is below 90 percent, go to “Device
Setup”, select “Calibration”, and perform oi Calibration.
4)
oi Fail Count
Number of consecutive oi failures counted (one passed oi test resets the
counter).
5) Consecutive
oi Fails
Set (allowable) number of consecutive oi failures to produce a fault.
6)
oi Calibrate Active (Y/n)
oi calibration is in progress.
7)
oi Calibrate Fault (Y/n) An
oi calibration fault has occurred.
8) manual
oi Active (Y/n)
A manual oi test is in progress.
9) manual
oi Fault (Y/n)
The detector has failed the last manual oi test.
Oi Menu
1) Left Oi
2) Middle Oi
3) Right Oi
4) Oi Fail Count
5) Consecutive Oi Fails
6) Oi Calibrate Active (Y/N)
7) Oi Calibrate Fault (Y/N)
8) Manual Oi Active (Y/N)
9) Manual Oi Fault (Y/N)
Device Info Menu
1) General Info Menu
2) HART Info Menu
3) Status Info Menu
4) Detector Settings
5) History Menu
X3302 Root Menu
1) Fire (Yes/No)
2) Fault (Yes/No)
3) Device Info Menu
4) Command Menu
5) Device Setup Menu
Status Info Menu
1) Warm Up (Y/N)
2) Fire (Y/N)
3) Automatic Oi Fault (Y/N)
4) Diminish. Detect. Flt (Y/N)
5) Detect. Disable Flt (Y/N)
6) Sensor Hdwr. Fault (Y/N)
7) HIB Hardware Fault (Y/N)
8) Internal Com. Flt (Y/N)
9) Incompatible Fault (Y/N)
10) Voltage Fault (Y/N)
11) Hardware Menu
12) Oi Menu