Det-Tronics X3302 Multispectrum IR Flame Detector with HART User Manual
Page 13

11
2.3
95-8613
hArdwAre menu
1) heater Power
Actual heater power (
0
to
100%
). Heater prevents condensation and icing on the
detector optics.
2) heater setpoint
Maximum amount of heater power allowed (in percent of full power).
3) Temperature
Actual internal temperature of detector.
4) Temp setpoint
Internal target temperature that the heater will attempt to maintain (in degrees C).
5) Temp range Fault
Detector integral temperature out of range — Operating range: –
40°
F to +
167°
F
(–
40°
C to +
75°
C).
6) voltage
Actual detector supply voltage (must be
18
to
30
Vdc).
7) voltage Fault (Y/n)
Supply voltage is out of range. Operating voltage must be
18
to
30
Vdc.
Hardware Menu
1) Heater Power
2) Heater Setpoint
3) Temperature
4) Temp Setpoint
5) Temp Range Fault
6) Voltage
7) Voltage Fault (Y/N)
Device Info Menu
1) General Info Menu
2) HART Info Menu
3) Status Info Menu
4) Detector Settings
5) History Menu
X3302 Root Menu
1) Fire (Yes/No)
2) Fault (Yes/No)
3) Device Info Menu
4) Command Menu
5) Device Setup Menu
Status Info Menu
1) Warm Up (Y/N)
2) Fire (Y/N)
3) Automatic Oi Fault (Y/N)
4) Diminish. Detect. Flt (Y/N)
5) Detect. Disable Flt (Y/N)
6) Sensor Hdwr Fault (Y/N)
7) HIB Hardware Fault (Y/N)
8) Internal Com. Flt (Y/N)
9) Incompatible Fault (Y/N)
10) Voltage Fault (Y/N)
11) Hardware Menu
12) Oi Menu