beautypg.com

Quick reference and default values – Despatch LCC1-51-3 User Manual

Page 75

background image

66

Quick Reference and Default Values


Program Page

Menu Item

Display

Default

Range

Setting

Ramp Time Seg 1

Pro-1 Seg-1 Ramp Time

00:00

00m00s to
99h59s

Event 1 Set Value

Pro-1 Seg-1 Ramp Event 1

Off

Off, On

Event 2 Set Value

Pro-1 Seg-1 Ramp Event 2

Off

Off, On

Event 3 Set Value

Pro-1 Seg-1 Ramp Event 3

Off

Off, On

Event 4 Set Value

Pro-1 Seg-1 Ramp Event 4

Off

Off, On

Soak Temp Seg 1

Pro-1 Seg 1 Soak Temp

68°F

SPLowerLim to
SPUpperLim *

Soak Time Seg 1

Pro-1 Seg 1 Soak Time

00:00

00m00s to
99h59s

Event 1 Set Value

Pro-1 Seg-1 Soak Event 1

Off

Off, On

Event 2 Set Value

Pro-1 Seg-1 Soak Event 2

Off

Off, On

Event 3 Set Value

Pro-1 Seg-1 Soak Event 3

Off

Off, On

Event 4 Set Value

Pro-1 Seg-1 Soak Event 4

Off

Off, On

(repeat for segments 2-8)

High Limit Setpoint

Pro-1 Hi-Lim SP

Max
HiLimSP

MinHiLimSP to
MaxHiLimSP *,
Band **

Loop From

Pro-1 Loop From XX

No

No, Seg-1 to
Seg-8

Loop To

Pro-1 Loop To XX

No

No, Seg-1 to
Seg-8

Loop Count

Pro-1 Loop Number

0

0 to 99

Profile Link

Pro-1 Link To XX

Stop

Standby***,
Stop, Hold,
Pro-1 to Pro-8

Guaranteed Soak

Pro-1 Guar Band

Off

Off, 1 to 760°C
(1400°F)

(repeat for profiles 2-8)


* See Enable Page
** Band value is set on Control Page
*** If Standby

1. Cycle Complete LED indication goes ON.
2. Controller beeps if End Of Cycle beep is enabled.
3. Heater/control output keeps controlling oven temperature at last Soak setpoint.
4. All events programmed (if relay cards installed and programmed as an event) for

the last Soak Segment stays active.