Despatch MIC1162 Hi-limit User Manual
Page 43

39
OUTPUT SPECIFICATIONS
OUTPUT 1 (Limit Relay)
Relay
Contact Type:
SPDT
Rating:
5A resistive at 120/240V AC
Lifetime:
> 100,000 operations at rated voltage/current
Isolation:
Inherent
OUTPUT 2 (Alarm or Annunciator)
Relay
Contact Type:
SPDT
Rating:
2A resistive at 120/240V AC
Lifetime:
> 500,000 operations at rated voltage/current
Isolation:
Inherent
OUTPUT 3 (Alarm, Annunciator, or Retransmit)
General
Types Available:
Relay or DC linear (retransmit only)
Relay
Contact Type:
SPDT
Rating:
2A resistive at 120/240V AC
Lifetime:
> 500,000 operations at rated voltage/current
Isolation:
Inherent
DC
Resolution:
Eight bits in 250mS (10 bits in 1 second typical, >10 bits in >1 second
typical).
Update Rate:
4 per second
Ranges:
0-20mA, 4-20mA, 0-10V, and 0-5V*
Load Impedance:
0-20mA:
500 ohm maximum
4-20mA:
500 ohm maximum
0- 10V:
500 ohm minimum
0-5V:
500 ohm minimum
Isolation: Isolated from all other inputs and outputs.
* Changes between V and mA ranges also require jumper movement.