39
 
 
 
 
 
OUTPUT SPECIFICATIONS 
 
OUTPUT 1 (Limit Relay) 
 
Relay 
Contact Type: 
SPDT
Rating:
5A resistive at 120/240V AC
Lifetime:
> 100,000 operations at rated voltage/current
Isolation:
Inherent
 
 
OUTPUT 2 (Alarm or Annunciator) 
 
Relay 
Contact Type: 
SPDT
Rating:
2A resistive at 120/240V AC
Lifetime:
> 500,000 operations at rated voltage/current
Isolation:
Inherent
 
OUTPUT 3 (Alarm, Annunciator, or Retransmit) 
 
General 
Types Available: 
Relay or DC linear (retransmit only)
 
Relay 
Contact Type: 
SPDT
Rating:
2A resistive at 120/240V AC
Lifetime:
> 500,000 operations at rated voltage/current
Isolation:
Inherent
 
DC 
Resolution: 
Eight bits in 250mS (10 bits in 1 second typical, >10 bits in >1 second 
typical). 
Update Rate:
4 per second
Ranges:
0-20mA, 4-20mA, 0-10V, and 0-5V*
Load Impedance:
0-20mA:
500 ohm maximum
4-20mA:
500 ohm maximum
0- 10V:
500 ohm minimum
0-5V:
500 ohm minimum
 
Isolation: Isolated from all other inputs and outputs. 
 
* Changes between V and mA ranges also require jumper movement. 