If the process variable attains a value lower than the input scale minimum, the upper
display will show:


If a break is detected in the sensor circuit, the upper display will show:


3.4 Front Panel Indicators


OUT Indicates the status of the Limit Relay. When the indicator is on, the relay is de-

energized, and when off, the relay is energized.


EXCEED

This indicator is on when the process variable exceeds the limit setpoint

(above for high limit, below for low limit). The indicator flashes if the error is not
acknowledged (i.e. Reset key is not pressed). The indicator is on steady if the
error has been acknowledged (i.e. Reset key has been pressed). Note: This
LED action will occur even if the annunciator output is NOT selected in
configuration.


ALM This indicator shows an alarm condition.

S

Indicates when in Set-Up mode.


3.5 Exceeding Limit Setpoint


If the process value exceeds the limit setpoint, the limit relay will change state and
latch. This is noted by the OUT indicator. The EXCEED indicator will also flash.

To acknowledge the limit condition, press the RESET key. If the process value
exceeds the limit setpoint, the EXCEED indicator will change to a steady on condition.
The EXCEED indicator will turn off once the process value no longer exceeds the limit
setpoint.

In order to reset the limit relay, the process value must not exceed the limit setpoint.
Pressing the RESET key with the control in this state will reset the limit relay, and the
OUT indicator will turn off.