Despatch MIC1162 Hi-limit User Manual
Page 34

30
4.
Apply power to the instrument and within 30 seconds of power-up, press and 
hold the DOWN and SCROLL keys simultaneously for about 5 seconds. The 
upper display will show ip_1 and the lower display will show CAL. 
 
5. 
Use the UP/DOWN keys as required to change the input type number as 
required: 
 
CAL INPUT NO. 
 
INPUT TYPE 
1
 
DC 0 - 50 mv 
2
 
DC 0 - 10 V 
3
 
DC 0 - 20 mA 
4
 
RTD 
5
 
Thermocouple 
 
NOTE: If required, only one input type may be calibrated. EXCEPTION: If it is required 
to calibrate the thermocouple input (Input Type 5), it is necessary to calibrate the DC 0 - 
50 mV (Input Type 1) first. 
 
6. 
Press the RESET key, the upper display will show _ _ _ _.
 
7. 
After a few seconds, the upper display will show ip_X, where X is the CAL INPUT 
No., if the calibration was successful. If the upper display shows FAIL, the 
calibration was not successful - check the jumper positions, wiring, CAL INPUT 
No. and try again. 
 
8. 
To calibrate all inputs, repeat steps 2 through 7 for each of the other input types.
 
9. 
The calibration procedure is now complete. Disconnect power, remove input 
connections. 