beautypg.com

Prepare site • assemble burner • mount burner, Verify clearances – Carlin 301CRD User Manual

Page 5

background image

Model 201CRD & 301CRD 240-VAC Advanced oil burners — Instruction manual

Carlin part number MN2301A Rev. 10/21/10

– 5 –

Combustion/ventilation air checklist

The burner may operate successfully under momentary

downdraft conditions, but sustained downdraft is unsafe.

• This can occur with an inadequate or incorrectly installed

chimney/vent.

• It can also occur in rooms/buildings equipped with exhaust

fans or unsealed return air ducts.

• Always check operation of the burner under all conditions

to verify vent system operates correctly.

• You may have to interlock the burner with exhaust fans to

shut burner off when fan operates; or provide make-up air
to the appliance room suffi cient to prevent any negative
pressure in the space.

• Failure to correct downdraft or negative room pressure

operation could result in severe personal injury, death or
substantial property damage.

• Gasoline or other fl ammable liquids or vapors.

• Combustible

materials.

• Air contaminants and chemicals, such as laundry products, paint, thinner,

varnish, etc.

materials at all times and that air openings will be kept unobstructed.

2. Prepare site • assemble burner • mount burner

(continued)

Verify clearances

Verify that the burner/appliance will maintain all required clearances:

manufacturer and local codes.

manual and applicable codes.

combustible construction, including the correct design of thimbles and
insulation where penetrating combustible walls.

Table 2

Minimum combustion/ventilation air openings

This manual is related to the following products: