Model 70200
Universal Oil Primary Control
Tech Support (800) 989-2275
www.carlincombustion.com
Installing and wiring
Warning — The 70200 control must be installed and serviced only by a qualified service technician.
1. Always disconnect power source before wiring to avoid electrical shock or damage to the control. All wiring must comply with applicable codes and
ordinances.
2. Thermostat terminals (T–T) provide a current source. Never apply external power to these terminals under any circumstances.
3. Alarm terminals provide a 24 VAC/VDC-rated dry contact, suitable for use with security/fire alarm systems.
Mounting
• The control may be mounted on a 4” x 4” junction box in any convenient location on the burner, furnace or wall. The location must not exceed the ambient
temperature limit, 140°F.
Wiring
• Wiring must comply with local and national electrical codes, and with the wiring diagram.
Power input
(red/white wire)
120 VAC, 60 HZ, 9VA
Limit circuit input
(black wire)
)
120 VAC, 60 HZ
Motor load
(orange wire)
10 FLA/ 60 LRA
(reduce by valve load)
Ignitor load
(blue wire)
)
120 VAC, 60 HZ, 500 VA
Vent Input
120 VAC, 60 HZ
Valve load
2 amps
Vent load
0.1 amp
Line Heater
1 amp
Alarm contacts
(dry contacts)
24V, AC/DC, 2A
Operating temperature limits
+32°F to +140°F
Storage temperature limits
-40°F to +185°F
Thermostat anticipator current 0.1 A, AC
Agencies
UL Recognized (US & Canada)
•
Replaces Carlin, Beckett, Honeywell and ICM
Primary Controls
•
On-Board LCD Screen
no special tool needed
•
Valve delay on (0, 3, 10, 15, 30, 60, 120)
•
Trial for ignition time (15, 30, 45)
•
Motor Delay Off (0, 10, 15, 30, 120, 300, 900)
•
Interrupted duty or Smart Ignition operation
•
Early Spark Termination Timing (0, -5, -10)
• Smart Ignition
•
Number of recycles (0, 3, Unlimited)
•
Serviceman reset protection (3)
•
TT Option (jumpered or open)
•
Blocked vent protection
•
Dry set of Alarm contacts
•
Built-in Pump Prime
•
Provides cad cell reading in OHMS
•
Fault history records last 50 fault cycles,
easy to understand icons displayed on screen
for common failures, Valve, Motor, Ignitor
Programmable, Microprocessor Based, Universal Replacement for CAD Cell Oil Burner