Website Alarms: the LOE’s trip relay outputs can be confi gured to report to the
levelandfl ow.com website whenever an alarm condi on is detected, regardless
of the sensors fi xed call-in interval. An Immediate alarm can then be setup on
the website to ini ate email and/or text message alerts whenever an alarm is
reported (see using the levelandfl ow website for more informa on).
NOTE: Immediate website alarms are subject to the Retry Time delay (30 to
180 second) as set in the LOE’s Basic Parameters page. Addi onal delays may
occur in establishing a connec on to the website, depending on the speed
and quality of the local internet connec on.
Confi guring the LOE for Website Alarms:
Placing a “1” in front of any of the Trip Types designates a closed or ac ve
output as an alarm condi on. For example; Trip Type 3 would be designated
as 13, and would send out an immediate alarm whenever the trip relay is
ac ve (closed).
Placing a “2” in front of any of the Trip Types designates an open or inac ve
output as an alarm condi on. For Example; Trip Type 3 would be designated
as 23, and would immediately report an alarm whenever the trip relay is
inac ve (open).
Alarm Filter: (located in the LOE’s Network Se ngs page) enabling the Alarm
Filtering op on can help prevent nuisance email and/or text message alerts
from being sent. If Alarm Filtering is enabled, all alarms condi ons that clear
before the Retry Time delay expires will not be reported to the website, and no
alert messages will be sent. If Alarm Filtering is disabled, all trip alarms will be
reported to the website (and alert messages sent), even if the alarm condi on
has cleared when the Retry Time expires.