Activate switch 1 if the event defined on row 2 arises and the condition defined on row
3 is met:

Action.ActivateSwitch: Switch=1; Event=2; Condition=3

Action.SetOutput

The

block defines the action necessary for setting of the intercom output to

SetOutput

the required level.

Parameters

Event – define the event that launches the action.
Condition – define the condition to be met to execute the action. This parameter
is optional.
Output – define the output to be set.

Valid values:

relay1 – relay 1 on basic unit
relay2 – relay 2 on basic unit
output1 – output 1 on basic unit
output2 – output 2 on basic unit
cr_relay1 – relay 1 on card reader
cr_relay2 – relay 2 on card reader
cr_output – output 1 on card reader
redled – red LED indicator
led1 – LED 1 indicator
led2 – LED 2 indicator
led3 – LED 3 indicator.

There may be different lists of valid values for different 2N Helios IP

®

models; refer to the Available Digital Inputs and Outputs subsection.

Level – define the required output level. This parameter is optional.

Valid values:

0 – output deactivation
1 – output activation (default value).

Example

Activate Output1 if the event defined on row 2 arises:

Action.SetOutput: Output=output1; Event=2

Action.BeginCall

The

block defines the action necessary for establishing of an outgoing call to

BeginCall

the defined telephone number, SIP URI or user number included in the intercom phone
book.