MCA/MOCP DETERMINATION NO C.O. OR UNPWRD C.O.

UN

IT

NOM.

V---Ph---Hz

IFM

TYPE

COMBUSTION

FAN MOTOR

FLA

POWER

EXHAUST

FLA

NO C.O. or UNPWRD C.O.

NO P.E.

w/ P.E. (pwrd fr/ unit)

MCA

MOCP

DISC. SIZE

MCA

MOCP

DISC. SIZE

FLA

LRA

FLA

LRA

580J

*08D

,F

208/230---3---60

STD

0.48

3.8

43.6

50

46

198

47.4

60

51

202

MED

45.9

50

49

235

49.7

60

53

239

HIGH

53.8

60

58

261

57.6

70

62

265

460---3---60

STD

0.25

1.8

20.1

25

21

97

21.9

25

23

99

MED

20.9

25

22

116

22.7

25

24

118

HIGH

25.3

30

27

129

27.1

30

29

131

575---3---60

STD

0.24

3.8

14.8

20

16

79

18.6

20

20

83

MED

15.2

20

16

94

19.0

25

21

98

HIGH

18.3

20

19

108

22.1

25

24

112

580J

*12D

,F

208/230---3---60

STD

0.48

3.8

48.5

60

51

263

52.3

60

56

267

MED

53.3

60

57

306

57.1

70

61

310

HIGH

58.3

70

62

315

62.1

70

67

319

460---3---60

STD

0.25

1.8

23.7

30

25

125

25.5

30

27

127

MED

25.5

30

27

147

27.3

30

29

149

HIGH

28.5

35

31

151

30.3

35

33

153

575---3---60

STD

0.24

3.8

17.9

20

19

95

21.7

25

23

99

MED

18.7

25

20

106

22.5

25

24

110

HIGH

21.5

25

23

120

25.3

30

27

124

580J

*14D

,F

208/230---3---60

STD

0.48

3.8

65.5

80

69

365

69.3

80

73

369

MED

68.0

80

72

382

71.8

80

76

386

HIGH

Model not available due to high amperage draw.

460---3---60

STD

0.25

1.8

31.7

40

33

183

33.5

40

35

185

MED

32.7

40

35

192

34.5

45

37

194

HIGH

35.7

45

38

196

37.5

45

40

198

575---3---60

STD

0.24

3.8

24.0

30

25

144

27.8

30

30

148

MED

24.0

30

25

144

27.8

30

30

148

HIGH

26.8

30

29

158

30.6

35

33

162

LEGEND:

CO

--- Convenient outlet

DISC

--- Disconnect

FLA

--- Full load amps

IFM

--- Indoor fan motor

LRA

--- Locked rotor amps

MCA

--- Minimum circuit amps

MOCP

--- Maximum over current protection

PE

--- Power exhaust

UNPWRD CO --- Unpowered convenient outlet

NOTES:

1. In compliance with NEC requirements for multimotor and

combination load equipment (refer to NEC Articles 430 and

440), the overcurrent protective device for the unit shall be

fuse or HACR breaker. Canadian units may be fuse or circuit

breaker.

2.

Unbalanced 3-Phase Supply Voltage

Never operate a motor where a phase imbalance in supply

voltage is greater than 2%. Use the following formula to

determine the percentage of voltage imbalance.

% Voltage Imbalance

= 100 x

max voltage deviation from average voltage

average voltage

Example: Supply voltage is 230-3-60

AB = 224 v
BC = 231 v
AC = 226 v

Average Voltage =

(224 + 231 + 226)

=

681

3

3

=

227

Determine maximum deviation from average voltage.
(AB) 227 – 224 = 3 v
(BC) 231 – 227 = 4 v
(AC) 227 – 226 = 1 v
Maximum deviation is 4 v.
Determine percent of voltage imbalance.

% Voltage Imbalance

= 100 x

4

227

= 1.76%

This amount of phase imbalance is satisfactory as it is below the

maximum allowable 2%.

IMPORTANT: If the supply voltage phase imbalance is more than

2%, contact your local electric utility company immediately.