INDICATORS

Normal State
The smoke detector operates in the normal state in the

absence of any trouble conditions and when its sensing

chamber is free of smoke. In the normal state, the Power

LED on both the sensor and the controller are on and all

other LEDs are off.
Alarm State
The smoke detector enters the alarm state when the

amount of smoke particulate in the sensor’s sensing

chamber exceeds the alarm threshold value. (See Table 3.)

Upon entering the alarm state:

S

The sensor’s Alarm LED and the controller’s Alarm LED

turn on.

S

The contacts on the controller’s two auxiliary relays

switch positions.

S

The contacts on the controller’s alarm initiation relay

close.

S

The controller’s remote alarm LED output is activated

(turned on).

S

The controller’s high impedance multiple fan shutdown

control line is pulled to ground Trouble state.

The SuperDuct duct smoke detector enters the trouble

state under the following conditions:

S

A sensor’s cover is removed and 20 minutes pass before

it is properly secured.

S

A sensor’s environmental compensation limit is reached

(100% dirty).

S

A wiring fault between a sensor and the controller is

detected.

An internal sensor fault is detected upon entering the

trouble state:

S

The contacts on the controller’s supervisory relay switch

positions. (See Fig. 29.)

S

If a sensor trouble, the sensor’s Trouble LED the

controller’s Trouble LED turn on.

S

If 100% dirty, the sensor’s Dirty LED turns on and the

controller’s Trouble LED flashes continuously.

S

If a wiring fault between a sensor and the controller, the

controller’s Trouble LED turns on but not the sensor’s.

Alarm

Power

Test/reset
switch

Trouble

C07298

Fig. 29 -- Controller Assembly

NOTE:

All troubles are latched by the duct smoke

detector. The trouble condition must be cleared and then
the duct smoke detector must be reset in order to restore it
to the normal state.
Resetting Alarm and Trouble Condition Trips
Manual reset is required to restore smoke detector systems

to Normal operation. For installations using two sensors,

the duct smoke detector does not differentiate which

sensor signals an alarm or trouble condition. Check each

sensor for Alarm or Trouble status (indicated by LED).

Clear the condition that has generated the trip at this

sensor. Then reset the sensor by pressing and holding the

reset button (on the side) for 2 seconds. Verify that the

sensor’s Alarm and Trouble LEDs are now off. At the

controller, clear its Alarm or Trouble state by pressing and

holding the manual reset button (on the front cover) for 2

seconds. Verify that the controller’s Alarm and Trouble

LEDs are now off. Replace all panels.

Troubleshooting

Controller’s Trouble LED is On

1. Check the Trouble LED on each sensor connected to

the controller. If a sensor’s Trouble LED is on, de-

termine the cause and make the necessary repairs.

2. Check the wiring between the sensor and the control-

ler. If wiring is loose or missing, repair or replace as

required.

Controller’s Trouble LED is Flashing

1. One or both of the sensors is 100% dirty.
2. Determine which Dirty LED is flashing then clean

that sensor assembly as described in the detector

cleaning section.

Sensor’s Trouble LED is On

1. Check the sensor’s Dirty LED. If it is flashing, the

sensor is dirty and must be cleaned.

2. Check the sensor’s cover. If it is loose or missing, se-

cure the cover to the sensor housing.

3. Replace sensor assembly.

Sensor’s Power LED is Off

1. Check the controller’s Power LED. If it is off, de-

termine why the controller does not have power and

make the necessary repairs.

2. Check the wiring between the sensor and the control-

ler. If wiring is loose or missing, repair or replace as

required.