The same equation can be used to determine the occupied

or maximum ventilation rate to the building. For example,

an output of 3.6 volts to the actuator provides a base

ventilation rate of 5% and an output of 6.7 volts provides

the maximum ventilation rate of 20% (or base plus 15 cfm

per person). Use Fig. 72 to determine the maximum

setting of the CO

2

sensor. For example, an 1100 ppm

setpoint relates to a 15 cfm per person design. Use the

1100 ppm curve on Fig. 72 to find the point when the CO

2

sensor output will be 6.7 volts. Line up the point on the

graph with the left side of the chart to determine that the

range configuration for the CO

2

sensor should be 1800

ppm. The EconoMi$er IV controller will output the 6.7

volts from the CO

2

sensor to the actuator when the CO

2

concentration in the space is at 1100 ppm. The DCV

setpoint may be left at 2 volts since the CO

2

sensor

voltage will be ignored by the EconoMi$er IV controller

until it rises above the 3.6 volt setting of the minimum

position potentiometer.

Once the fully occupied damper position has been

determined, set the maximum damper demand control

ventilation potentiometer to this position. Do not set to the

maximum position as this can result in over-ventilation to

the space and potential high humidity levels.
CO

2

Sensor Configuration

The CO

2

sensor has preset standard voltage settings that

can be selected anytime after the sensor is powered up.

(See Table 23.)
Use setting 1 or 2 for Bryant equipment. (See Table 23.)

1. Press Clear and Mode buttons. Hold at least 5

seconds until the sensor enters the Edit mode.

2. Press Mode twice. The STDSET Menu will appear.

Table 23 – CO

2

Sensor Standard Settings

SETTING

EQUIPMENT

OUTPUT

VENTILATION

RATE

(cfm/Person)

ANALOG

OUTPUT

CO

2

CONTROL

RANGE

(ppm)

OPTIONAL

RELAY SETPOINT

(ppm)

RELAY

HYSTERESIS

(ppm)

1

Interface w/Standard

Building Control System

Proportional

Any

0---10V

4---20mA

0---2000

1000

50

2

Proportional

Any

2---10V

7---20mA

0---2000

1000

50

3

Exponential

Any

0---10V

4---20mA

0---2000

1100

50

4

Economizer

Proportional

15

0---10V

4---20mA

0---1100

1100

50

5

Proportional

20

0---10V

4---20mA

0---900

900

50

6

Exponential

15

0---10V

4---20mA

0---1100

1100

50

7

Exponential

20

0---10V

4---20mA

0---900

900

50

8

Health & Safety

Proportional

0---10V

4---20mA

0---9999

5000

500

9

Parking/Air Intakes/

Loading Docks

Proportional

0---10V

4---20mA

0---2000

700

50

580J