beautypg.com

Caution, Burners and igniters – Bryant F User Manual

Page 27

background image

27

HEATER TUBE

ASSEMBLY

SEAL STRIPS,

SPONGE RUBBER

REGULATOR

GASKET

REGULATOR

RETAINER

WIND CAP

ASSEMBLY

(SHOWN

INVERTED,

AS SHIPPED)

BURNER ASSEMBLY

INDUCER FAN-MOTOR ASSEMBLY

SUPPORT INSULATION ASSEMBLY

C08227

Fig. 34 -- Heat Exchanger Assembly

Burners and Igniters

EQUIPMENT DAMAGE HAZARD
Failure to follow this caution may result in

equipment damage.
When working on gas train, do not hit or plug

orifice spuds.

CAUTION

!

Main Burners
To access burners, remove burner access panel and slide

out burner partition. At the beginning of each heating

season, inspect for deterioration or blockage due to

corrosion or other causes. Observe the main burner flames

and adjust, if necessary.
Orifice Projection
Refer to Fig. 35 for maximum projection dimension for

orifice face to manifold tube.

ORIFICE

1.00-in

(25.4 mm)

MANIFOLD

PIPE

C08211

Fig. 35 -- Orifice Projection

Removal and Replacement of Gas Train
See Fig. 30, 34, and 36.

1. Shut off manual gas valve.
2. Shut off power to unit.
3. Slide out burner partition.
4. Disconnect gas piping at unit gas valve.
5. Remove wires connected to gas valve. Mark each

wire.

580J