NOTE: The default value for the evaporator--fan motor

on/off delay is 45 seconds. The Integrated Gas Unit
Controller (IGC) modifies this value when abnormal limit
switch cycles occur. Based upon unit operating conditions,
the on delay can be reduced to 0 seconds and the off delay
can be extended to 180 seconds.
If the limit switch trips at the start of the heating cycle

during the evaporator on delay, the time period of the on

delay for the next cycle will be 5 seconds less than the

time at which the switch tripped. (Example: If the limit

switch trips at 30 seconds, the evaporator--fan on delay for

the next cycle will occur at 25 seconds.) To prevent

short--cycling, a 5--second reduction will only occur if a

minimum of 10 minutes has elapsed since the last call for

heating.

The evaporator--fan off delay can also be modified. Once

the call for heating has ended, there is a 10--minute period

during which the modification can occur. If the limit

switch trips during this period, the evaporator--fan off

delay will increase by 15 seconds. A maximum of 9 trips

can occur, extending the evaporator-fan off delay to 180

seconds.

To restore the original default value, reset the power to the

unit.

To shut off unit, set system selector switch at OFF

position. Resetting heating selector lever below room

temperature will temporarily shut unit off until space

temperature falls below thermostat setting.

Ventilation (Continuous Fan)

Set fan and system selector switches at ON and OFF

positions,

respectively.

Evaporator

fan

operates

continuously to provide constant air circulation. When the

evaporator-fan selector switch is turned to the OFF

position, there is a 30--second delay before the fan turns

off.

START--UP, RTU--MP CONTROL

Field Service Test, explained below, will assist in proper

start--up. Configuration of unit parameters, scheduling

options, and operation are also discussed in this section.

Field Service Test

The Field Service Test function can be used to verify

proper operation of compressors, heating stages, indoor

fan,

power

exhaust

fans,

economizer,

and

dehumidification. Use of Field Service Test is

recommended at initial system start up and during

troubleshooting. See RTU--MP Controls, Start--Up,

Operation, and Troubleshooting Instructions (Form

48--50H--T--2T), Appendix A for Field Service Test Mode

table.

Field Service Test mode has the following changes from

normal operation:

S

Outdoor air temperature limits for cooling circuits,

economizer, and heating are ignored.

S

Normal compressor time guards and other staging delays

are ignored.

S

The status of Alarms (except Fire and Safety chain) is

ignored but all alerts and alarms are still broadcasted on

the network.

Field Service Test can be turned ON/OFF at the unit

display or from the network. Once turned ON, other

entries may be made with the display or through the

network. To turn Field Service Test on, change the value

of Test Mode to ON, to turn Field Service Test off, change

the value of Test Mode to OFF.
NOTE: Service Test mode is password protected when
accessing from the display. Depending on the unit model,
factory--installed options, and field--installed accessories,
some of the Field Service Test functions may not apply.
The independent outputs (IndpOutputs) submenu is used

to change output status for the supply fan, economizer,

and Power Exhaust. These independent outputs can

operate simultaneously with other Field Service Test

modes. All outputs return to normal operation when Field

Service Test is turned off.
The Cooling submenu is used to change output status for

the individual compressors and the dehumidification relay.

Compressor starts are not staggered. The fans and heating

service test outputs are reset to OFF for the cooling

service test. Indoor fans and outdoor fans are controlled

normally to maintain proper unit operation. All normal

cooling alarms and alerts are functional.
NOTE: Circuit A is always operated with Circuit B due
to outdoor fan control on Circuit A. Always test Circuit A
first, and leave it on to test other Circuits.
The Heating submenu is used to change output status for

the individual heat stages, gas or electric. The fans and

cooling service test outputs are reset to OFF for the

heating service test. All normal heating alarms and alerts

are functional.

Configuration

The RTU--MP controller configuration points affect the

unit operation and/or control. Review and understand the

meaning and purpose of each configuration point before

changing it from the factory default value. The submenus

containing configuration points are as follows: Unit,

Cooling, Heating, Inputs, Economizer, IAQ, Clock--Set,

and User Password (USERPW). Each configuration point

is described below under its according submenu. See

RTU--MP

Controls,

Start--Up,

Operation,

and

Troubleshooting Instructions (Form 48--50H--T--2T),

Appendix for display tables.
Unit
Start Delay
This refers to the time delay the unit will wait after power

up before it pursues any specific operation.

Factory Default = 5 sec

Range = 0--600 sec