Table 11 – Orifice Sizes
ORIFICE
DRILL SIZE
BRYANT
PART NUMBER
DRILL
DIA. (in.)
#30
LH32RF129
0.1285
1/8
LH32RF125
0.1250
#31
LH32RF120
0.1200
#32
LH32RF116
0.1160
#33
LH32RF113
0.1130
#34
LH32RF111
0.1110
#35
LH32RF110
0.1100
#36
LH32RF105
0.1065
#37
LH32RF104
0.1040
#38
LH32RF102
0.1015
#39
LH32RF103
0.0995
#40
LH32RF098
0.0980
#41
LH32RF096
0.0960
#42
LH32RF094
0.0935
#43
LH32RF089
0.0890
#44
LH32RF086
0.0860
#45
LH32RF082
0.0820
#46
LH32RF080
0.0810
#47
LH32RF079
0.0785
#48
LH32RF076
0.0760
#49
LH32RF073
0.0730
#50
LH32RF070
0.0700
#51
LH32RF067
0.0670
#52
LH32RF065
0.0635
#53
LH32RF060
0.0595
#54
LH32RF055
0.0550
#55
LH32RF052
0.0520
#56
LH32RF047
0.0465
#57
LH32RF043
0.0430
#58
LH32RF042
0.0420
Table 12 -- Altitude Compensation* (08--14)
ELEVATION
ft (m)
125,000
BTUH Nominal
250,000
BTUH Nominal
180,000, 224,000
BTUH Nominal
NG Orifice
Size
LP Orifice
Size
NG Orifice
Size
LP Orifice
Size
NG Orifice
Size
LP Orifice
Size
0 --- 2000 (610)
31
1
49
3
†30
46
3
31
1
48
3
2000 (610)
32
1
50
3
†30
47
3
32
1
49
3
3000 (914)
32
1
50
3
31
1
47
3
32
1
49
3
4000 (1219)
33
1
50
3
31
1
48
3
33
1
49
3
5000 (1524)
33
1
51
4
31
1
48
3
33
1
50
3
6000 (1829)
34
1
51
4
31
1
48
3
34
1
50
3
7000 (2134)
35
1
51
4
32
1
49
3
35
1
50
3
8000 (2438)
36
1
52
4
33
1
49
3
36
1
51
4
9000 (2743)
37
2
52
4
34
1
50
3
37
2
51
4
10000 (3048)
38
2
52
4
35
1
50
3
38
2
52
4
11000 (3353)
39
2
53
4
36
1
51
4
39
2
52
4
12000 (3658)
†41
53
4
37
2
51
4
†41
53
4
13000 (3962)
†42
54
4
38
2
52
4
†42
53
4
14000 (4267)
†43
54
4
†40
53
4
†43
54
4
LEGEND
NG = Natural Gas
LP = Liquid Propane
* As the height above sea level increases, there is less oxygen
per cubic ft. of air. Therefore, heat input rate should be reduced
at higher altitudes.
{
Not included in kit. May be purchased separately through
dealer.
1 = CRLPELEV001A00
2 = CRLPELEV002A00
3 = CRLPELEV003A00
4 = CRLPELEV004A00
580J