Fig. 26 -- Typical Smoke Detector System Wiring

Highlight B
Smoke detector NC contact set will open on smoke alarm

condition, de--energizing the ORN conductor.
Highlight C
24--v power signal via ORN lead is removed at Smoke

Detector input on LCTB; all unit operations cease

immediately.
RTU--MP Controls
Unit operating functions (fan, cooling and heating) are

terminated as described above. In addition:
Highlight D
On smoke alarm condition, the smoke detector NO Alarm

contact will close, supplying 24--v power to GRA

conductor.
Highlight E
GRA lead at Smoke Alarm input on LCTB provides 24--v

signal to FIOP DDC control.
RTU--MP
The 24--v signal is conveyed to RTU--MP’s J1--10 input

terminal. This signal initiates the FSD sequence by the

RTU--MP control. FSD status is reported to connected

BAS network.
Using Remote Logic
Five conductors are provided for field use (see Highlight

F) for additional annunciation functions.

Additional Application Data — Refer to Catalog No.

HKRNKA--1XA for discussions on additional control

features of these smoke detectors including multiple unit

coordination. (See Fig. 26.)

Sensor and Controller Tests

Sensor Alarm Test
The sensor alarm test checks a sensor’s ability to signal an

alarm state. This test requires that you use a field provided

SD--MAG test magnet.

OPERATIONAL TEST HAZARD
Failure to follow this caution may result in personnel

and authority concern.
This test places the duct detector into the alarm state.

Unless part of the test, disconnect all auxiliary

equipment from the controller before performing the

test. If the duct detector is connected to a fire alarm

system,

notify

the

proper

authorities

before

performing the test.

CAUTION

!

Sensor Alarm Test Procedure

1. Hold the test magnet where indicated on the side of

the sensor housing for seven seconds.

2. Verify that the sensor’s Alarm LED turns on.
3. Reset the sensor by holding the test magnet against

the sensor housing for two seconds.

4. Verify that the sensor’s Alarm LED turns off.