Regulatory compliance, Table 24, Regulatory – Brocade Communications Systems Brocade VDX 8770-4 User Manual
Page 98: Compliance

78
Brocade VDX 8770-4 Hardware Reference Manual
53-1002563-02
Regulatory compliance
A
Regulatory compliance
This section describes the regulatory compliance requirements for the Brocade VDX 8770-4. It
contains the following standards:
TABLE 24
NEBS installation requirements for the Brocade VDX 8770-4
Reference
Warning, requirement, or statement
Intrabuilding or Intra-connection
WARNING: The intra-building copper Ethernet ports of the equipment or
subassembly are suitable for connection to intrabuilding or unexposed
wiring or cabling only. The intra-building port(s) of the equipment or
subassembly MUST NOT be metallically connected to interfaces that
connect to the outside plant (OSP) or its wiring. These interfaces are
designed for use as intra-building interfaces only (Type 2 or Type 4 ports
as described in GR-1089-CORE, Issue 6) and require isolation from the
exposed OSP cabling. The addition of Primary Protectors is not sufficient
protection in order to connect these interfaces metallically to OSP wiring
First Level Lightning Criteria AC Power
Ports
WARNING: The Brocade VDX 8770-4 shall be connected to and external
Special Protection Devices (SPD) when installed and connected to
commercial AC power.
Class A2 Voltage Accessibility
The Brocade VDX 8770-4 shall be located in a restricted access location
were only crafts personnel are allowed access.
Class B Voltage Accessibility
The Brocade VDX 8770-4 shall be located in a restricted access location
were only crafts personnel are allowed access.
Equipment Grounding Systems
The Brocade VDX 8770-4 shall be installed and connected to the CBN,
IBN or Ether.
Communication Equipment Grounding
The Brocade VDX 8770-4 is suitable for connection to the Central Office.
Bonding of Battery Return (BR) Input
Terminals
The battery returns of the Brocade VDX 8770-4 shall be connected as (,
DC-I).
Connections
The Brocade VDX 8770-4 shall be grounded via a copper ground
conductor.
Connections
All bare grounding connection points to the Brocade VDX 8770-4 shall be
cleaned and coated with an anti-oxidant solution before connections are
made.
Connections
All surfaces on the Brocade VDX 8770-4 that are un-plated shall be
brought to a bright finish and treated with and anti-oxidant solution
before connections is made.
Connections
All non-conductive surfaces on the Brocade VDX 8770-4 shall be
removed from all threads and connection points to ensure electrical
continuity
Connections
Brocade VDX 8770-4 utilizes a 2-hole compression type, Agency
approved crimped connector with a copper #2 American Wire Gauge
(AWG) that is utilizes 20 inch pounds of torque to secure it the frame and
EUT.
Input DC Voltage
The Brocade VDX 8770-4 is capable of operating at 200-240 V, 50/60
Hz at a maximum current level 16.0 A max., or -48VDC, 70.0 A max. per
power supply.