beautypg.com

Bryant 551C User Manual

Page 59

background image

59

Table 36—Perfect HumidityAdaptive Dehumidification System Subcooling Mode Service Analysis

PROBLEM

CAUSE

REMEDY

Subcooling Mode (Liquid Reheat)

Will Not Energize.

No power to control transformer from

evaporator-fan motor.

Check power source and evaporator-fan relay. Ensure all

wire connections are tight.

Will Not Energize.

No power from control transformer to liquid line

solenoid valve.

1. Fuse open; check fuse. Ensure continuity of wiring.

2. Low-pressure switch open. Cycle unit off and allow

low-pressure switch to reset. Replace switch if it will

not close.

3. Transformer bad; check transformer.

Liquid line solenoid valve will not operate.

1. Solenoid coil defective; replace.

2. Solenoid valve stuck open; replace.

Liquid line solenoid valve will not open.

Valve is stuck closed; replace valve.

Low System Capacity.

Low refrigerant charge or frosted evaporator coil.

1. Check charge amount. Charge per Fig. 53---56.

2. Evaporator coil frosted; check and replace low-pres-

sure switch if necessary.

Loss of Compressor Superheat

Conditions with Subcooling/Reheat

Dehumidification Coil Energized.

Thermostatic expansion valve (TXV).

1. Check TXV bulb mounting, and secure tightly to suc-

tion line.

2. Replace TXV if stuck open or closed.

Table 37—Perfect HumidityAdaptive Dehumidification System Hot Gas Reheat Mode Service Analysis

PROBLEM

CAUSE

REMEDY

Reheat Mode Will Not Energize.

No power to control transformer from

evaporator-fan motor.

Check power source and evaporator-fan relay. Ensure all

wire connections are tight.

No power from control transformer to hot gas

line solenoid valve

1. Fuse open; check fuse. Ensure continuity of wiring.

2. Low-pressure switch open. Cycle unit off and allow

low-pressure switch to reset. Replace switch if it will

not close.

3. Transformer bad; check transformer.

Hot gas line solenoid valve will not operate.

1. Solenoid coil defective; replace.

2. Solenoid valve stuck closed; replace.

Low refrigerant charge or frosted evaporator coil.

1. Check charge amount. Charge per Fig. 53---56.

2. Evaporator coil frosted; check and replace low-pres-

sure switch if necessary.

Loss of Compressor Superheat

Conditions with Subcooling/Reheat

Dehumidification Coil Energized.

Thermostatic expansion valve (TXV).

1. Check TXV bulb mounting, and secure tightly to suc-

tion line.

2. Replace TXV if stuck open or closed.

Excessive Superheat.

Liquid line solenoid valve will not operate.

Valve is stuck, replace valve.

Excessive Superheat.

Hot gas line solenoid valve will not close.

Valve is stuck; replace valve.

Table 38—EconoMi$er IV Input/Output Logic

INPUTS

OUTPUTS

Demand Control

Enthalpy*

Compressor

N Terminal†

Demand Control

V til ti

(DCV)

Outdoor

Return Y1 Y2

Stage Stage

Occupied

Unoccupied

Ventilation (DCV)

Outdoor

Return Y1 Y2

1

2

Damper

Below set

(DCV LED Off)

High

(F

C li

LED Off)

Low

On On

On

On

Minimum position

Closed

Below set

(DCV LED Off)

High

(Free Cooling LED Off)

Low

On Off

On

Off

Minimum position

Closed

Off Off

Off

Off

Low

(F

C li

LED O )

High

On On

On

Off

Modulating** (between min.

i i

d f ll

)

Modulating** (between

l

d

d f ll

)

Low

(Free Cooling LED On)

High

On Off

Off

Off

Modulating

(between min.

position and full-open)

Modulating

(between

closed and full-open)

Off Off

Off

Off

Minimum position

Closed

Above set

(DCV LED O )

High

(F

C li

LED Off)

Low

On On

On

On

Modulating†† (between min.

i i

d DCV

i

)

Modulating†† (between

l

d

d DCV

Above set

(DCV LED On)

High

(Free Cooling LED Off)

Low

On Off

On

Off

Modulating†† (between min.

position and DCV maximum)

Modulating†† (between

closed and DCV

maximum)

Off Off

Off

Off

maximum)

Low

(F

C li

LED O )

High

On On

On

Off

Modulating***

Modulating†††

Low

(Free Cooling LED On)

High

On Off

Off

Off

Modulating

Modulating†††

Off Off

Off

Off

*For single enthalpy control, the module compares outdoor enthalpy to the ABCD set point.

†Power at N terminal determines Occupied/Unoccupied setting: 24 vac (Occupied), no power (Unoccupied).

**Modulation is based on the supply-air sensor signal.

††Modulation is based on the DCV signal.

***Modulation is based on the greater of DCV and supply-air sensor signals, between minimum position and either maximum position (DCV) or fully open (sup-

ply-air signal).

†††Modulation is based on the greater of DCV and supply-air sensor signals, between closed and either maximum position (DCV) or fully open (supply-air sig-

nal).

551B

,C

This manual is related to the following products: