beautypg.com

T oa ) + (tr, Ra ) t (t, 100 ) + (tr – Bryant 551C User Manual

Page 30: 100 ) =t, 551b ,c

background image

30

A proportional anticipatory strategy should be taken with the
following conditions: a zone with a large area, varied occupancy,

and equipment that cannot exceed the required ventilation rate at
design conditions. Exceeding the required ventilation rate means

the equipment can condition air at a maximum ventilation rate

that is greater than the required ventilation rate for maximum
occupancy. A proportional-anticipatory strategy will cause the

fresh air supplied to increase as the room CO

2

level increases

even though the CO

2

set point has not been reached. By the time

the CO

2

level reaches the set point, the damper will be at

maximum ventilation and should maintain the set point.
In order to have the CO

2

sensor control the economizer damper in

this manner, first determine the damper voltage output for
minimum or base ventilation. Base ventilation is the ventilation

required to remove contaminants during unoccupied periods. The

following equation may be used to determine the percent of
outside-air entering the building for a given damper position. For

best results there should be at least a 10 degree difference in
outside and return-air temperatures.

(T

OA

) + (TR

x

RA

) T

(T

O x

100 )

+ (TR

x

100 ) =T

M

T

O

= Outdoor-Air Temperature

OA = Percent of Outdoor Air

T

R

= Return-Air Temperature

RA = Percent of Return Air
T

M

= Mixed-Air Temperature

Once base ventilation has been determined, set the minimum
damper position potentiometer to the correct position.
The same equation can be used to determine the occupied or

maximum ventilation rate to the building. For example, an output
of 3.6 volts to the actuator provides a base ventilation rate of 5%

and an output of 6.7 volts provides the maximum ventilation rate
of 20% (or base plus 15 cfm per person). Use Fig. 38 to

determine the maximum setting of the CO

2

sensor. For example,

a 1100 ppm set point relates to a 15 cfm per person design. Use
the 1100 ppm curve on Fig. 38 to find the point when the CO

2

sensor output will be 6.7 volts. Line up the point on the graph
with the left side of the chart to determine that the range

configuration for the CO

2

sensor should be 1800 ppm. The

EconoMi$er IV controller will output the 6.7 volts from the CO

2

sensor to the actuator when the CO

2

concentration in the space is

at 1100 ppm. The DCV set point may be left at 2 volts since the
CO

2

sensor voltage will be ignored by the EconoMi$er IV

controller until it rises above the 3.6 volt setting of the minimum
position potentiometer.
Once the fully occupied damper position has been determined, set

the maximum damper demand control ventilation potentiometer
to this position. Do not set to the maximum position as this can

result in over-ventilation to the space and potential high-humidity
levels.
CO

2

Sensor Configuration

The CO

2

sensor has preset standard voltage settings that can be

selected anytime after the sensor is powered up. (See Table 7.)

TR1

24 Vac

COM

TR

24

Vac

HOT

1

2

3

4

5

EF

EF1

+

_

P1

T1

P

T

N

EXH

2V

10V

EXH

Set

Set

2V

10V

2V

10V

DCV

DCV

Free

Cool

B

C

A

D

SO+

SR+

SR

SO

AQ1

AQ

DCV

Min

Pos

Open

Max

N1

C06038

Fig. 37

--- EconoMi$er IV Control

0

1000

2000

3000

4000

5000

6000

2

3

4

5

6

7

8

800 ppm
900 ppm
1000 ppm
1100 ppm

RANGE

CONFIGURA

TION

(ppm)

DAMPER VOLTAGE FOR MAX VENTILATION RATE

CO SENSOR MAX RANGE SETTING

2

C06039

Fig. 38

--- CO

2

Sensor Maximum Range Setting

Use setting 1 or 2 for Bryant equipment. (See Table 7.)

1. Press Clear and Mode buttons. Hold at least 5 seconds

until the sensor enters the Edit mode.

2. Press Mode twice. The STDSET Menu will appear.
3. Use the Up/Down button to select the preset number. (See

Table 7.)

4. Press Enter to lock in the selection.
5. Press Mode to exit and resume normal operation.

The custom settings of the CO

2

sensor can be changed anytime

after the sensor is energized. Follow the steps below to change the
non-standard settings:

1. Press Clear and Mode buttons. Hold at least 5 seconds

until the sensor enters the Edit mode.

2. Press Mode twice. The STDSET Menu will appear.
3. Use the Up/Down button to toggle to the NONSTD menu

and press Enter.

4. Use the Up/Down button to toggle through each of the

nine variables, starting with Altitude, until the desired

setting is reached.

5. Press Mode to move through the variables.
6. Press Enter to lock in the selection, then press Mode to

continue to the next variable.

551B

,C

This manual is related to the following products: