beautypg.com

Bryant 551C User Manual

Page 24

background image

24

C06131

Fig. 19

--- Outdoor--Air Damper With Hood Attached

C06132

Fig. 20

--- Outdoor--Air Damper Position Setting

ECONOMI$ER IV

CONTROLLER

OUTSIDE AIR

TEMPERATURE SENSOR

LOW AMBIENT

SENSOR

ACTUATOR

WIRING

HARNESS

C06021

Fig. 21

--- EconoMi$er IV Component Locations

Optional EconoMi$er IV
See Fig. 21 for EconoMi$er IV component locations.
NOTE:

These instructions are for installing the optional

EconoMi$er IV only. Refer to the accessory EconoMi$er IV
installation instructions when field installing an EconoMi$er IV
accessory.

1. To remove the existing unit filter access panel, raise the

panel and swing the bottom outward. The panel is now

disengaged from the track and can be removed. (See
Fig. 22.)

2. The box with the economizer hood components is shipped

in the compartment behind the economizer. The
EconoMi$er IV controller is mounted on top of the

EconoMi$er IV. To remove the component box from its
shipping position, remove the screw holding the hood box

bracket to the top of the economizer. Slide the hood box
out of the unit. (See Fig. 23.)

IMPORTANT: If the power exhaust accessory is to be installed
on the unit, the hood shipped with the unit will not be used and
must be discarded. Save the aluminum filter for use in the power
exhaust hood assembly.

3. The indoor coil access panel will be used as the top of the

hood. Remove the screws along the sides and bottom of

the indoor coil access panel. (See Fig. 24.)

4. Swing out indoor coil access panel and insert the hood

sides under the panel (hood top). Use the screws provided
to attach the hood sides to the hood top. Use screws
provided to attach the hood sides to the unit. (See Fig. 25.)

5. Remove the shipping tape holding the economizer

barometric relief damper in place.

6. Insert the hood divider between the hood sides. (See

Fig. 25 and 26.) Secure hood divider with 2 screws on
each hood side. The hood divider is also used as the

bottom filter rack for the aluminum filter.

7. Open the filter clips which are located underneath the

hood top. Insert the aluminum filter into the bottom filter
rack (hood divider). Push the filter into position past the
open filter clips. Close the filter clips to lock the filter into

place. (See Fig. 26.)

8. Caulk the ends of the joint between the unit top panel and

the hood top. (See Fig. 24.)

9. Replace the filter access panel.

10. Install all EconoMi$er IV accessories. EconoMi$er IV

wiring is shown in Fig. 27.

Barometric flow capacity is shown in Fig. 28. Outdoor air

leakage is shown in Fig. 29. Return air pressure drop is shown in

Fig. 30.

FILTER ACCESS PANEL

OUTDOOR-AIR OPENING AND

INDOOR COIL ACCESS PANEL

COMPRESSOR

ACCESS PANEL

C06023

Fig. 22

--- Typical Access Panel Locations

551B