beautypg.com

551b ,c – Bryant 551C User Manual

Page 27

background image

27

Outdoor Enthalpy Changeover
For enthalpy control, accessory enthalpy sensor (part number

HH57AC078) is required. Replace the standard outdoor dry bulb
temperature sensor with the accessory enthalpy sensor in the same

mounting location. (See Fig. 21.) When the outdoor air enthalpy
rises above the outdoor enthalpy changeover set point, the

outdoor-air damper moves to its minimum position. The outdoor

enthalpy changeover set point is set with the outdoor enthalpy set
point potentiometer on the EconoMi$er IV controller. The set

points are A, B, C, and D. (See Fig. 36.) The factory-installed
620-ohm jumper must be in place across terminals SR and SR+

on the EconoMi$er IV controller. (See Fig. 21 and 37.)
Differential Enthalphy Control
For differential enthalpy control, the EconoMi$er IV controller
uses

two

enthalpy

sensors

(HH57AC078

and

CRENTDIF004A00), one in the outside air and one in the return

air duct. The EconoMi$er IV controller compares the outdoor air
enthalpy to the return air enthalpy to determine EconoMi$er IV

use. The controller selects the lower enthalpy air (return or
outdoor) for cooling. For example, when the outdoor air has a

lower enthalpy than the return air, the EconoMi$er IV opens to

bring in outdoor air for free cooling.

0

500

1000

1500

2000

2500

0.05

0.15

0.25

STATIC PRESSURE (in. wg)

FLOW

IN

CUBIC

FEET

PER

MINUTE

(cfm)

C06030

Fig. 28

--- Barometric Flow Capacity

0

5

10

15

20

25

30

0.13 0.20 0.22 0.25 0.30 0.35 0.40 0.45 0.50

STATIC PRESSURE (in. wg)

FLOW

IN

CUBIC

FEET

PER

MINUTE

(cfm)

C06031

Fig. 29

--- Outdoor--Air Damper Leakage

0

1000

2000

3000

4000

5000

6000

0.05

0.10

0.15

0.20

0.25

0.30

0.35

STATIC PRESSURE (in. wg)

FLOW

IN

CUBIC

FEET

PER

MINUTE

(cfm)

C06032

Fig. 30

--- Return--Air Pressure Drop

+

C7400A1004

HH57AC078 ENTHALPY

SENSOR

MOUNTING PLATE

C06361

Fig. 31

--- Enthalpy Sensor and Mounting Plate

SUPPLY AIR

TEMPERATURE

SENSOR

MOUNTING

LOCATION

SUPPLY AIR

TEMPERATURE

SENSOR

C06033

Fig. 32

--- Supply Air Sensor Location

551B

,C

This manual is related to the following products: