The liquid enters the evaporator coil at a temperature lower than
in standard cooling operation. This lower temperature increases

the latent capacity of the rooftop unit. The refrigerant passes
through the evaporator and is turned into a vapor. The air passing

over the evaporator coil will become colder than during normal

operation. However, as this same air passes over the subcooling
coil, it will be slightly warmed, partially reheating the air.
Subcooling mode operates only when the outside air
temperature is warmer than 40_F. A factory-installed temperature

switch located in the condenser section will lock out subcooling

mode when the outside temperature is cooler than 40_F.
The scroll compressors are equipped with crankcase heaters to

provide protection for the compressors due to the additional
refrigerant charge required by the subcooling/reheat coil.
When in subcooling mode, there is a slight decrease in system

total gross capacity (5% less), a lower gross sensible capacity
(20% less), and a greatly increased latent capacity (up to 40%

more).

C06135

Fig. 42

--- Perfect Humidityt Normal

Design Cooling Operation

C06136

Fig. 43

--- Perfect Humidity Subcooling

Mode Operation

C06137

Fig. 44

--- Perfect Humidity Hot Gas

Reheat Mode Operation

Hot Gas Reheat Mode
When the humidity levels in the space require humidity control, a

hot gas solenoid valve (specific to hot gas reheat mode only) will
open to bypass a portion of hot gas refrigerant around the

condenser coil. (See Fig. 44.)
This hot gas will mix with liquid refrigerant leaving the

condenser

coil

and

flow

to

the

subcooling/reheat

dehumidification coil. Now the conditioned air coming off the
evaporator will be cooled and dehumidified, but will be warmed

to neutral conditions (72_F to 75_F) by the subcooling/reheat
dehumidification coil.
The net effect of the rooftop when in hot gas reheat mode is to

provide nearly all latent capacity removal from the space when
sensible loads diminish (when outdoor temperature conditions are

moderate). When in hot gas reheat mode, the unit will operate to
provide mostly latent capacity and extremely low sensible heat

ratio capability.
Similar to the subcooling mode of operation, hot gas reheat mode
operates only when the outside air temperature is warmer than

40_F. Below this temperature, a factory installed outside air
temperature switch will lockout this mode of operation.
See Table 34 for the Perfect Humidity adaptive dehumidification
system sequence of operation.

SERVICE

ELECTRICAL SHOCK HAZARD
Failure to follow this warning could cause personal

injury or death.
When sevicing unit, shut off all electrical power to unit

and install lockout tag.

!

WARNING

Step 1

—Cleaning

Inspect unit interior at the beginning of heating and cooling
season and as operating conditions require.
Evaporator Coil

1. Turn unit power off, tag disconnect. Remove evaporator

coil access panel.

2. If economizer or two-position damper is installed, remove

economizer

by

disconnecting

Molex

plug

and

removing mounting screws.

3. Slide filters out of unit.