beautypg.com

551b ,c, Dc b a – Bryant 551C User Manual

Page 29

background image

29

LED ON

LED ON

LED ON

LED ON

LED OFF

19

18

LED OFF

LED OFF

LED OFF

17

16

15

14

13

12

11

10

9

40

45

50

55

60

65

70

75

80

85

90

95 100

DEGREES FAHRENHEIT

mA

D

C

B

A

C06035

Fig. 34

--- Outside Air Temperature

Changeover Set Points

ECONOMI$ER IV

ECONOMI$ER IV

CONTROLLER

GROMMET

RETURN AIR

SENSOR

RETURN DUCT

(FIELD-PROVIDED)

C06036

Fig. 35

--- Return Air Temperature or Enthalpy

Sensor Mounting Location

CONTROL

CURVE

A
B
C
D

CONTROL POINT

APPROX.

deg. F (deg. C)

AT 50% RH

73 (23)
70 (21)
67 (19)
63 (17)

12

1

4

1

6

18

20

2

2

24

26

28

30

32

3

4

36

38

40

42

44

46

9

0

1

0

0

80

70

6

0

50

40

30

20

10

ENTHALPY BTU PER POUND DRY AIR

85

(29)

90

(32)

95

(35)

100

(38)

105

(41)

110

(43)

35

(2)

35

(2)

40

(4)

40

(4)

105

(41)

110

(43)

45

(7)

45

(7)

50

(10)

50

(10)

55

(13)

55

(13)

60

(16)

60

(16)

65

(18)

65

(18)

70

(21)

70

(21)

75

(24)

75

(24)

80

(27)

80

(27)

85

(29)

90

(32)

95

(35)

100

(38)

A

A

B

B

C

C

D

D

RELATIVE HUMIDITY (%)

HIGH LIMIT

CURVE

APPROXIMATE DRY BULB TEMPERATURE--degrees F (degrees C)

C06037

Fig. 36

--- Enthalpy Changeover Set Points

Occupancy Control
The factory default configuration for the EconoMi$er IV control

is occupied mode. Occupied mode is provided by the black
jumper from terminal TR to terminal N. When unoccupied mode

is desired, install a field-supplied timeclock function in place of
the jumper between TR and N. (See Fig. 27.) When the timeclock

contacts are closed, the EconoMi$er IV control will be in

occupied mode. When the timeclock contacts are open (removing
the 24-v signal from terminal N), the EconoMi$er IV will be in

unoccupied mode.

Demand Controlled Ventilation (DCV)
When using the EconoMi$er IV for demand controlled

ventilation, there are some equipment selection criteria which
should be considered. When selecting the heat capacity and cool

capacity of the equipment, the maximum ventilation rate must be
evaluated for design conditions. The maximum damper position

must be calculated to provide the desired fresh air.
Typically the maximum ventilation rate will be about 5 to 10%
more than the typical cfm required per person, using normal

outside air design criteria.

551B

,C

This manual is related to the following products: