beautypg.com

551b ,c – Bryant 551C User Manual

Page 26

background image

26

EconoMi$er IV Control Modes
Determine the EconoMi$er IV control mode before set up of the

control. Some modes of operation may require different
sensors. (See Table 6.) The EconoMi$er IV is supplied from the

factory with a supply--air temperature sensor and an outdoor-- air
temperature sensor. This allows for operation of the EconoMi$er

IV with outdoor air dry bulb changeover control. Additional

accessories can be added to allow for different types of
changeover control and operation of the EconoMi$er IV and unit.

Table 6—EconoMi$er IV Sensor Usage

APPLICATION

ECONOMI$ER IV WITH OUTDOOR AIR

DRY BULB SENSOR

APPLICATION

Accessories Required

Outdoor Air

Dry Bulb

None. The outdoor air dry bulb sensor

is factory installed.

Differential

Dry Bulb

CRTEMPSN002A00*

Single Enthalpy

HH57AC078

Differential

Enthalpy

HH57AC078

and

CRENTDIF004A00*

CO

2

for DCV

Control using a

Wall-Mounted

CO

2

Sensor

33ZCSENCO2

CO

2

for DCV

Control using a

Duct-Mounted

CO

2

Sensor

33ZCSENCO2†

and

33ZCASPCO2**

O

R

CRCBDIOX005A00††

*CRENTDIF004A00 and CRTEMPSN002A00 accessories are used on many

different base units. As such, these kits may contain parts that will not be

needed for installation.

† 33ZCSENCO2 is an accessory CO

2

sensor.

** 33ZCASPCO2 is an accessory aspirator box required for duct-mounted

applications.

†† CRCBDIOX005A00 is an accessory that contains both 33ZCSENCO2

and 33ZCASPCO2 accessories.

Outdoor Dry Bulb Changeover
The standard controller is shipped from the factory configured for

outdoor dry bulb changeover control. The outdoor--air and
supply--air temperature sensors are included as standard. For this

control mode, the outdoor temperature is compared to an
adjustable set point selected on the control. If the outdoor-air

temperature is above the set point, the EconoMi$er IV will adjust

the outdoor-air dampers to minimum position. If the outdoor air
temperature is below the set point, the position of the outdoor air

dampers will be controlled to provide free cooling using outdoor
air. When in this mode, the LED next to the free cooling set point

potentiometer will be on. The changeover temperature set point is

controlled by the free cooling set point potentiometer located on
the control. (See Fig. 33.) The scale on the potentiometer is A, B,

C, and D. See Fig. 34 for the corresponding temperature
changeover values.
Differential Dry Bulb Control
For differential dry bulb control the standard outdoor dry bulb

sensor is used in conjunction with an additional accessory dry
bulb sensor (part number CRTEMPSN002A00). The accessory

sensor must be mounted in the return airstream. (See Fig. 35.)

Wiring is provided in the EconoMi$er IV wiring harness. (See
Fig. 27.)
In this mode of operation, the outdoor-air temperature is
compared to the return-air temperature and the lower temperature

airstream is used for cooling. When using this mode of

changeover control, turn the enthalpy setpoint potentiometer fully
clockwise to the D setting. (See Fig. 33.)

FOR OCCUPANCY CONTROL

REPLACE JUMPER WITH

FIELD-SUPPLIED TIME CLOCK

LEGEND

DCV— Demand Controlled Ventilation

IAQ — Indoor Air Quality

LA — Low Ambient Lockout Device

OAT — Outdoor-Air Temperature

POT — Potentiometer

RAT — Return-Air Temperature

Potentiometer Defaults Settings:

Power Exhaust Middle

Minimum Pos.

Fully Closed

DCV Max.

Middle

DCV Set

Middle

Enthalpy

C Setting

NOTES:

1. 620 ohm, 1 watt 5% resistor should be removed only when using differential

enthalpy or dry bulb.

2. If a separate field-supplied 24 v transformer is used for the IAQ sensor power

supply, it cannot have the secondary of the transformer grounded.

3. For field-installed remote minimum position POT, remove black wire jumper

between P and P1 and set control minimum position POT to the minimum

position.

8

7

C06028

Fig. 27

--- EconoMi$er IV Wiring

551B

,C

This manual is related to the following products: