Table 34—Perfect Humidity Adaptive Dehumidification System Sequence of Operation and

System Response — Single Compressor Unit (551C 024--060, 551B 036--072)

THERMOSTAT INPUT

ECONOMIZER FUNCTION

551B,C UNIT OPERATION

H

Y1

Y2

OAT. < Economizer Set Point

Economizer

Comp. 1

Subcooling Mode

Hot Gas Reheat Mode

Off

Normal Operation

On

On

On

No

Off

On

Yes

No

On

On

Off

No

Off

On

Yes

No

On

On

On

Yes

On

On

Yes

No

On

On

Off

Yes

On

On

No

Yes

On

Off

Off

No

Off

On

No

Yes

NOTE: On a thermostat call for W1, all cooling and dehumidification will be off.

LEGEND

OAT --- Outdoor Air Temperature

Step 3

—Condenser--Fan Adjustment

Shut off unit power supply. Remove condenser-fan assembly
(grille, motor, motor cover, and fan) and loosen fan hub

setscrews. Adjust fan height as shown in Fig. 50. Tighten

setscrews and replace condenser-fan assembly.

UNIT

FAN HEIGHT (in.) - A

024-060 and 072 (208/230 v)

072 (460 v)

2.75

3.50

C06138

Fig. 48

--- Condenser--Fan Adjustment

Step 4

—EconoMi$er IV Adjustment

Refer to Optional EconoMi$er IV section.

Step 5

—Refrigerant Charge

Amount of refrigerant charge is listed on unit nameplate (also

refer to Table 1). Refer to HVAC Servicing Procedures literature
available at your local distributor and the following procedures.
Unit panels must be in place when unit is operating during
charging procedure. Unit must operate a minimum of 10 minutes

before checking or adjusting refrigerant charge.
No Charge
Use standard evacuating techniques. After evacuating system to
500 microns, weigh in the specified amount of refrigerant. (Refer

to Table 1 and unit information plate.)
Low Charge Cooling
Using Cooling Charging Charts, Fig. 49--52, vary refrigerant

until the conditions of the charts are met. Note the charging charts
are different from type normally used. Charts are based on

charging the units to the correct superheat for the various
operating conditions. Accurate pressure gauge and temperature

sensing device are required. Connect the pressure gauge to the

service port on the suction line. Mount the temperature sensing
device on the suction line and insulate it so that outdoor ambient

temperature does not affect the reading. Indoor-air cfm must be
within the normal operating range of the unit. An accurate

superheat, thermocouple--type or thermistor--type thermometer,
and a gauge manifold are required when using the superheat

charging method for evaluating the unit charge. Do not use

mercury or small dial--type thermometers because they are not
adequate for this type of measurement.

C06139

Fig. 49

--- Cooling Charging Chart,

Standard 551B 036

Perfect HumiditySystem Charging
The system charge for units with the Perfect Humidity adaptive

dehumidification system is greater than that of the standard unit
alone. The charge for units with this option is indicated on the

unit nameplate drawing. Also refer to Fig. 53--56. To charge
systems using the Perfect Humidity adaptive dehumidification

system, fully evacuate, recover, and recharge the system to the

nameplate specified charge level. To check or adjust refrigerant
charge on systems using the Perfect Humidity adaptive

dehumidification system, charge per Fig. 53--56.