beautypg.com

Warning – Howard HI-110 Network Transformer User Manual

Page 9

background image

Document 2.4.128, Revision 2

August, 2012

9

Network Transformer Instruction Manual

Lifting and Handling

Lifting hooks are provided near the top of the

transformer tank for lifting. All four lifting hooks

must be used simultaneously. The transformer must

not be lifted from any points other than the provided

lifting hooks. Do not use holes in the lifting hooks for

lifting. These holes are for tie-down purposes only

and are not suitable for lifting. Do not use the cover-

mounted lifting eyes for lifting the entire transformer,

as these lifting eyes are suitable for lifting the cover

plate only.

Transformers should be lifted in an upright position,

allowing the transformer to tilt no more than 15

degrees from vertical. Lifting cables should be

no more than 20

degrees from vertical. Spreader

bars should be used to keep the lifting cables

nearly vertical, enabling a safe lift and reducing the

likelihood of tank deformation or damage to painted

surfaces.

Lifting the transformer with a forklift is not

recommended, since weight and balance can be

problematic and radiator panels can be easily

damaged. Refer to the transformer nameplate

to determine the total weight of the assembled

transformer. Special care must be taken when

handling transformers when the ambient

temperature is below minus 20

°C (minus 4°F);

otherwise, permanent damage to the transformer

may result.

WARNING

FAILURE TO FOLLOW THE INSTRUCTIONS

BELOW COULD RESULT IN DEATH OR SERIOUS

PERSONAL INJURY AND MAY ALSO RESULT IN

DAMAGE TO THE EQUIPMENT.
• Use a crane, suitable lifting cables or

straps, and a spreader bar to unload the

transformer.

• Do not unload using a forklift.
• Keep unnecessary personnel clear while

unloading and moving the transformer.

Jacking

The transformer base is designed for jacking. Do

not use radiator fins, bushings, valves, gauges or

sheet metal surfaces for jacking. Jacking must

be done using the proper jacking provisions from

two adjacent corners simultaneously to prevent

warping of the tank bottom. Do not allow the jack to

come into contact with panel radiators. Refer to the

transformer outline drawing for the total weight of

the assembled transformer.

Location and Mounting

Consult local and national codes to ensure that

the installation meets all applicable requirements.

Location of the transformer must permit it to operate

in conditions that meet the requirements specified

in the “Usual Service Conditions” section of IEEE

Standard C57.12.00. Operation not meeting these

service condition requirements will compromise

transformer capacity and reliability, unless the

transformer is designed specifically for operation

in conditions other than usual service conditions.

Contact the Howard Industries Transformer

Division, if additional information is needed about

location and mounting issues not covered by these

instructions.

The transformer should be mounted on a level

concrete foundation of sufficient strength to support

the weight of the completely assembled transformer

including the network protector and any other

attached accessories. The transformer should sit

flush with the surface of the mounting surface, so

that the transformer’s weight is evenly distributed.

The installed transformer should not tilt in any

direction more than three degrees. Greater tilt may

compromise insulation fluid coverage of live parts

and may prevent insulating fluid from circulating

properly through the cooling radiators. Improper

circulation of insulating fluid may cause overheating

and result in reduced transformer life.

When network transformers are installed in vaults or

compartments, it is necessary to provide adequate

ventilation. The amount of air flow necessary will

SECTION 3: INSTALLATION