Page 27

background image

Document 2.4.128, Revision 2

August, 2012

27

Network Transformer Instruction Manual

Table 6: Torque Guidelines for Accessories

Component

Nominal

Torque

¹

(in-lbs)

Torque

Range

(in-lbs)

Fluid level sight glass

600

480-720

Fill plug

960

900-1020

Drain plug

960

900-1020

Drain valve

600

480-720

Automatic pressure

relief device, ¼” NPT

180

160-200

Automatic pressure

relief device, cover-

mounted

300

250-350

Ground connector

160

140-180

¹ When checking tightness of gasketed components,

the measured torque will normally be less than

the nominal torque listed in the table above due

to relaxation of the gasket material. Additional

tightening of mounting hardware may cause the

component to crack or the gasket to become over-
compressed.

Additional Maintenance Instructions

These instructions are intended to be a general

guide for the maintenance of Howard secondary

network transformers, when used in typical

applications and operated in usual environments

as described in IEEE Standard C57.12.00. Although

efforts have been made to ensure accuracy and

completeness, these instructions do not address

every conceivable application or circumstance that

might be encountered.

Features and accessory devices discussed herein

may not be present in all transformers. Some

features or accessory devices may be present on a

transformer, but not discussed in these instructions.

Howard Industries does not represent that these

instructions are complete, sufficient, accurate or

useful for all circumstances.

Questions regarding installation, operation, and

maintenance (particularly when encountering

unusual or special circumstances not sufficiently

covered by these instructions) should be directed to

the Howard Industries Transformer Division.

Repair Parts

Repair parts can be ordered from the Howard

Industries Transformer Division. A description of

the part and the transformer serial number will be

required to ensure that the correct part has been

ordered.

Warranty Claims

The Howard Industries Transformer Division

should be notified immediately when problems are

discovered during the warranty period. All warranty

repairs must be made or approved by the Howard

Industries Transformer Division.