beautypg.com

Warning, Danger – Howard HI-110 Network Transformer User Manual

Page 22

background image

Document 2.4.128, Revision 2

August, 2012

22

Network Transformer Instruction Manual

8. Check all fasteners for signs of corrosion and

replace as necessary.

9. Check fluid temperature gauges, including the

maximum temperature drag hand (if present)

to determine whether the fluid temperature has

exceeded the design limit. Any such indication

should be investigated to determine and correct

the cause.

10. Check torque values on all ground connections

and tighten as necessary. Refer to torque

guidelines contained in Table 6.

11. Replace any damaged or unreadable

nameplates, instructional labels and safety

labels.

12. If it is suspected that water or other

contaminants may have entered the main

tank, switch chamber or terminal chamber,

the fluid or compound should be tested to

determine its condition. For transformers

filled with conventional transformer oil,

Refer to IEEE Standard C57.106, Guide for

Acceptance and Maintenance of Insulating Oil

in Equipment. For transformer filled with less-

flammable high molecular weight hydrocarbon

insulating fluid (such as R-Temp), refer to IEEE

Standard C57.212, Guide for Acceptance and

Maintenance of Less Flammable Hydrocarbon

Fluids in Transformers. For transformers filled

with silicone fluid or seed-based fluid (such

as Envirotemp FR3), contact the Howard

Industries Transformer Division for testing

recommendations.

13. Lubricate external parts of the primary

disconnect and grounding switch at least

annually.

14. Exercise the primary disconnect and grounding

switch at least annually.

Electrical Testing

The following electrical tests should be used to

determine the condition of the transformer. Follow

the instructions and precautions provided by the

test equipment manufacturer. Contact the Howard

Industries Transformer Division to discuss any of

these tests.

FAILURE TO FOLLOW THE INSTRUCTIONS

BELOW COULD RESULT IN DEATH OR

SERIOUS PERSONAL INJURY AND MAY ALSO

RESULT IN DAMAGE TO THE EQUIPMENT.

• Do not energize the transformer using

single-phase switches or fuses. Use only

gang-operated three-phase switches to

energize a three-phase transformer

• Do not operate the transformer with any of

the primary phases open.

• Only qualified personnel with appropriate

equipment should measure transformer

voltages.

• Wear personal protective equipment (PPE)

to prevent injury from potential arc flash or

contact with dangerous voltages.

• Make sure the transformer is securely and

effectively grounded at all times.

• CT leads must be connected to the

metering load or shorted together and

grounded to prevent dangerous voltages

at the CT terminals.

WARNING

DANGER

FAILURE TO FOLLOW THE INSTRUCTIONS BELOW

WILL RESULT IN DEATH OR SERIOUS PERSONAL

INJURY AND MAY ALSO RESULT IN DAMAGE TO

THE EQUIPMENT.

Be aware of dangerous voltages and avoid

personal contact with live terminals