beautypg.com

Warning – Howard HI-110 Network Transformer User Manual

Page 24

background image

Document 2.4.128, Revision 2

August, 2012

24

Network Transformer Instruction Manual

Other Accessory Devices

Other accessories devices, such as a gauges and

valves typically require no maintenance except for

replacement in the event of malfunction or damage.

Sampling and Testing the Fluid

Before sampling the insulating fluid, de-energize

the transformer and make sure all bushings and

terminals are effectively grounded. Samples should

be drawn from the bottom of the tank. Refer to

ASTM D923 Standard Practices for Sampling

Electrical Insulating Liquids for recommended

sampling procedures. Also refer to any sampling

recommendations supplied by the fluid test

equipment manufacturer.

It is recommended that a fluid sample be drawn

annually and tested for dielectric strength. Dielectric

strength should measure at least 26 kV.

Filtering the Fluid

Insulating fluids such as mineral oil, R-Temp or

seed-based fluids can be filtered using a filter

press system. A filter press can remove particle

contaminants as well as small amounts of moisture.

Follow the operating instructions provided by the

filter press system manufacturer.

Continue to filter the fluid until the dielectric test

result is 26kV or better. When filtering any particular

type of insulating fluid, make sure the filter press

system is not contaminated with any other type

of fluid. Contamination of the fluid may alter its

chemical or physical characteristics and could

reduce its fire point.

Removing or Lowering the Fluid

Should it be necessary to remove or lower the

insulating fluid, the following procedure should be

used.

1. De-energize the transformer and make

sure the tank, bushings, and terminals are

effectively grounded.

2. If cover removal is required, remove cover

as outlined in the “Opening the Transformer

Tank” section.

3. Use a clean, dry temporary storage container

to contain the fluid.

4. Use clean pumps and hoses that have not

been contaminated by different types of

fluids. Hoses must be designed for handling

the particular fluid in the transformer (As an

example, rubber hoses should not be used

with mineral oil.).

5. Connect the pump intake line to the drain

valve at the bottom of the transformer tank.

6. Place the pump discharge line nozzle at the

bottom of storage container.

7. Pump slowly and do not allow the fluid to

splash into the container, as this will introduce

air and moisture into the fluid.

8. Do not lower the insulating fluid below top

of core/coil clamp pan unless absolutely

necessary. Exposing coils may allow moisture

to contaminate coil insulation.

Filling with Fluid

When refilling the transformer with insulating fluid, fill

with the same type of fluid. Do not mix different types

of fluids. Care should be taken to avoid introduction

of air bubbles during the filling process. After refilling

is complete, allow 24 hours for dissipation of air

bubbles before energizing the transformer. Trapped

air bubbles can reduce the insulating value of the

fluid and cause an internal flash-over.
1. Every storage container or tote of transformer

fluid should be visually inspected and tested for

WARNING

FAILURE TO FOLLOW THE INSTRUCTIONS

BELOW COULD RESULT IN DEATH OR SERIOUS

PERSONAL INJURY AND MAY

ALSO RESULT IN

DAMAGE TO THE EQUIPMENT.

• Release internal pressure before opening the

tank. Personnel should wear eye and skin

protective equipment when using the pressure

relief valve to relieve tank presure. Hot fluid

may be expelled.

• Never allow anyone to enter the transformer

tank until an analysis of the air inside the tank

indicates at least 19.5% oxygen.

• Whenever someone is inside the tank, a

person should be stationed outside the tank

to ensure the safety of the person inside the

tank.