beautypg.com

Howard HI-110 Network Transformer User Manual

Page 12

background image

Document 2.4.128, Revision 2

August, 2012

12

Network Transformer Instruction Manual

board located under oil in the transformer

tank. Refer to “Opening the Transformer

Tank” for instructions.

4. Tap Changer Setting

For transformers supplied with high-voltage

taps, check the tap changer setting to

ensure it is set to the proper position for the

required voltage. The tap changer setting

must not be changed while the transformer

is energized. Unless otherwise specified,

tapped transformers will be shipped from the

factory with the tap switch set to the nominal

position.

5. Series/Multiple and Delta/Wye Switch

Settings

For transformers supplied with a delta/

wye and/or series/multiple switch, check

switch settings to make sure they are set to

the correct position. If delta/wye or series/

multiple connections are made using an

internal terminal board instead of a switch,

check to ensure that these connections are

made properly according to the chart on the

transformer nameplate. Refer to “Opening

the Transformer Tank” for instructions.

Neither the series/multiple nor delta/wye

switch setting should be changed while the

transformer is energized. Unless otherwise

specified, transformers are shipped from the

factory with series/multiple and delta/wye

connections set to the highest voltage.

6. Grounding

Check to ensure that the transformer tank is

permanently and effectively grounded.

7. Bolted Connections

Check all bolted connections for tightness,

referring to nominal torque guidelines

contained in Tables 3 through 6.

8. Fluid Levels

The transformer main tank and primary

switch chamber are shipped from the factory

with insulating fluid filled to the proper level,

indicated by the 25

°C mark on the fluid level

gauge. Before energizing the transformer,

verify proper fluid levels by observing the

gauges. Be aware that fluid levels vary with

fluid temperature. A transformer found to

have a low fluid level should be checked for

potential leaks, repaired as necessary and

filled to the proper level with the same type

of liquid as specified on the transformer

nameplate. When wiping sleeve entrances

are provided, the terminal chamber is

shipped dry, unless otherwise specified by

the customer.

9. Fluid Temperature

Before energizing the transformer, observe

the fluid temperature gauge and make sure

the temperature is no lower than the values

listed below.

-20°C (-4°F) for conventional

transformer oil and silicone fluid

-0°C (32°F) for R-Temp fluid

-10°C (14°F) for FR3 fluid

10. Current Transformers

If current transformers (CTs) are supplied,

connect CT leads to a metering load. If CT

leads are not connected to a metering load,

they must be shorted together and grounded

before the transformer is energized.

11. Accessory Wiring

Check the wiring of control and alarm

circuits, if supplied, to make sure there are

no loose connections and no damage to wire

insulation.

12. Tank Finish

Check all painted surfaces to make sure that

there is no damage or corrosion.

13. Tools

Check to make sure that all tools and

equipment are accounted for.

14. Internal Inspection

The transformer main tank is sealed and

should not be opened unless necessary. If

the transformer main tank must be opened,

refer to “Opening the Transformer Tank” for

instructions. Contact the Howard Industries

Transformer Division prior to opening the

tank.