beautypg.com

Warning – Howard HI-110 Network Transformer User Manual

Page 21

background image

Document 2.4.128, Revision 2

August, 2012

21

Network Transformer Instruction Manual

WARNING

FAILURE TO FOLLOW THE INSTRUCTIONS

BELOW COULD RESULT IN DEATH OR

SERIOUS PERSONAL INJURY, AND

MAY ALSO RESULT IN DAMAGE TO THE

EQUIPMENT.
The transformer must be de-energized

before performing any maintenance work.

Transformers should be inspected periodically

while in service, with the frequency of inspection

determined by service conditions. Transformers

operating in unusual service conditions should be

inspected more frequently. Refer to IEEE Standard

C57.12.00 for a discussion of usual and unusual

service conditions.
Accessories such as PRVs, PRDs, temperature

gauges, fluid level gauges and drain valves typically

require no maintenance, except replacement in

the event of damage. Gauges should be checked

periodically to make sure they are operating properly.
When performing periodic maintenance, the checks

described below should be made at a minimum.

Periodic Inspection

All exterior surfaces of the transformer and the

transformer’s surroundings should be inspected.

Inspection frequency should be governed by

operating conditions at the installation site.

More severe conditions indicate the need for more

frequent inspection.

Inspection and Maintenance Checklist

While observing safe working practices, perform the

following checks.
1. Inspect for dents or other damage to metal

surfaces and make the necessary repairs

2. Inspect the paint finish for damage, corrosion

or weathering that exposes the primer coat or

bare metal. Repair any paint damage that might

be found. Refer to “Exterior Paint Finish” for

instructions.

3. Inspect thoroughly for evidence of fluid leaks,

including main tank, switch chamber, terminal

chamber, radiators, bushings, gauges, switches,

valves and all other accessories. Check fluid

level gauges or sight glasses to determine

fluid levels in all compartments. If a leak is

suspected, perform a pressure test according to

the instructions in “Pre-energization Inspection

and Tests.” Add fluid as necessary to ensure

that the proper fluid level is maintained. Repair

as necessary. Fluid leaks must be repaired

immediately to prevent serious damage to the

transformer and danger to personnel. Refer to

Fluid Leaks” for instructions.

4. Visually check all gaskets for cracking or other

signs of deterioration. Replace as necessary.

When replacing a gasket carefully clean mating

surfaces to remove any rust, dirt, transformer

fluid, old gasket material, or other contamination

that might prevent a good seal. Use appropriate

gasket cement when installing new gaskets. Do

not reuse old gaskets. Six months after replacing

a gasket, check and re-tighten if necessary, being

careful not to overtighten.

5. Maintain a clean and unobstructed area around

the transformer, including sufficient clearance

around radiators to ensure adequate cooling of

the transformer.

6. Inspect the base of the transformer main tank

and make sure that there is no accumulated dirt

or other debris that might promote corrosion.

7. Check bushings, gauges, valves, switches and

all other accessories for proper operation, and

repair or replace any defective devices.

SECTION 7: MAINTENANCE