Storage requirements – Bell & Gossett P81673 REV I Series 1510 User Manual

Page 11

background image

Examples

Figure 1: Example of a proper lifting method

Figure 2: Example of a proper lifting method using lifting lugs

Storage requirements

If the unit will not to be installed and put into operation immediately upon arrival at the
site, or for an extended shutdown after the unit is in operation, the following requirements
for short-term storage apply:

• Store in a covered and dry location.
• Store the unit free from excessive cold or heat (below 32°F and above 110°F), dirt,

and vibration.

• Rotate the shaft by hand several times (10–15 turns) at least every 30 days.

For initial storage longer than three months, or for pump shut down after being in
operation longer than three months, contact your local sales and service representative
for long-term storage guidelines.

Transportation and Storage

Series 1510 Installation, Operation, and Maintenance Manual

9