NOVUS AUTOMATION

3/5

Configuration level

0PEr

0PEr

0PEr

0PEr

Operation Mode

The NT240 has 11 pre-defined operating modes
plus the possibility for the user to create his own
customized mode. The operation modes are
described with further details in the section "Timer
Operation Modes".

0

0

0

0 Delayed output following power on

1

1

1

1 Delayed pulse after power on

2

2

2

2 Pulse on power on

3

3

3

3 Cyclic after power on

4

4

4

4 Pulse after momentary input signal

5

5

5

5

Extended pulse after release of the input

signal

6

6

6

6

Delayed output after momentary signal in the

input

7

7

7

7

Delayed pulse after momentary signal in the

input

8

8

8

8 Pulse after continuous signal in the input

9

9

9

9 Delayed output following continuous input

signal

10

10

10

10 Delayed pulse after continuous input signal

11 Special mode defined by the user

1.rA

1.rA

1.rA

1.rA

Temporization ranges: sets the interval range to
be used by the timer, as below:

0

0

0

0: 99.99 s

4

4

4

4: 9999 min

1

1

1

1: 999.9 s

5

5

5

5: 99 h 59 min

2

2

2

2: 9999 s

6

6

6

6: 9999 h

3

3

3

3: 99 min 59 s

T1.uP

T1.uP

T1.uP

T1.uP

Defines the count mode presentation to the
display:

0: down counting
1: up counting

F Fu

F Fu

F Fu

F Fu

Function of the front panel

F

key:

0

0

0

0: The

F

key is not used;

1

1

1

1: Reset – Resets time counting;

2

2

2

2: Reset and Hold – Restarts or pauses time

counting. The key function depends on operation
mode chosen for the timer, as described in the
section "Timer Operation Modes".

PnP

PnP

PnP

PnP

Defines the type of the signal to be applied to the
timer input.

0: Sensor with open collector NPN output or dry
contact;

Sensor with open collector PNP output or logical
DC pulse

Ov1.r

Ov1.r

Ov1.r

Ov1.r

Output temporization range, to be used by the
0u1.t

0u1.t

0u1.t

0u1.t parameter.

0

0

0

0: 99.99 s

4

4

4

4: 9999 min

1

1

1

1: 999.9 s

5

5

5

5: 99 h 59 min

2

2

2

2: 9999 s

6

6

6

6: 9999 h

3

3

3

3: 99 min 59 s

Custom Operating Mode Level

NOTE: The parameters in the Custom Operating Mode level are
automatically set by the timer when a predefined operating mode is
selected (0PEr

0PEr

0PEr

0PEr = 0

0

0

0 to

10

10

10

10

). The parameters below are used when

the user needs to customized the timer to a particular mode of
operation (0PEr

0PEr

0PEr

0PEr = 11

11

11

11).

t1.S1

t1.S1

t1.S1

t1.S1

Temporization Start. This parameter defines when
the temporization should be initiated:

0

0

0

0 : On timer power-up.

1

1

1

1 : Upon Start input activation (leading edge of

the Start input).

2

2

2

2 : Upon Start input being released (trailing edge

of the Start input)

3

3

3

3 : Start input leading edge only when the output

is off

4

4

4

4 : Start input trailing edge only when the output

is off

5

5

5

5 : Through the

F

key. The Function

programmed for the

F

key must be Reset

and Hold (FFv

FFv

FFv

FFv = 2

2

2

2).

t1.S2

t1.S2

t1.S2

t1.S2

Defines the timer action when the start input is
activated during the temporization:

0

0

0

0 : Restarts temporization
1

1

1

1 : Disregard the Start input when the

temporization is in progress

2

2

2

2 : Interrupts temporization.

t1.S3

t1.S3

t1.S3

t1.S3

This parameter defines the moment the output is
to be activated:

0

0

0

0: At the leading edge of the Start input signal.
1

1

1

1: At the trailing edge of the Start Input signal.
2

2

2

2: At the beginning of the temporization.
3

3

3

3: At the end of the temporization.

t1.S4

t1.S4

t1.S4

t1.S4

This parameter defines how the output is to be
turned off:

0

0

0

0: At the end of the programmed time interval;

1

1

1

1: After the output temporization, as defined in

ou1.t

ou1.t

ou1.t

ou1.t;

2

2

2

2: Only by the Reset command.

The Reset can be accomplished either by the
Reset input of by the

F

key programmed with

Reset function (FFv

FFv

FFv

FFv = 1

1

1

1).

T1.S5

T1.S5

T1.S5

T1.S5

Automatic temporization restart. Allows cyclical
temporization, according to the values below:

0

0

0

0: No automatic restart.
1

1

1

1: Restart at the end of the temporization (as

defined in t1.SP

t1.SP

t1.SP

t1.SP).

2

2

2

2: Restart after the end of the output

temporization (t1.SP

t1.SP

t1.SP

t1.SP + 0vt.1

0vt.1

0vt.1

0vt.1

)

PARAMETER CHANGE WHILE TEMPORIZATION IS
IN PROGRESS

When a parameter in the programming cycles of the timer is modified
by the user, the temporization in progress is interrupted and the timer
reset.

Do not change timer configuration while the temporization
is performing critical functions, as the outputs may be
turned on and off at improper moments.