beautypg.com

Mechanical installation, Electrical connections, Electrical connections – 0-10 vdc input – NOVUS TxIsoRail 4-20 mA User Manual

Page 2

background image

NOVUS AUTOMATION

2/3

The TxConfig screen in shown in Fig 3.

Fig. 3 – TxConfig main screen

The fields in the screen mean:
1. Input Sensor: Choose the desired temperature sensor among the

available options. See Table 1.

2. Measuring Range: Defines the beginning and the end of the range.
When the Low Scale Limit is configured with a value higher than the Full

Scale Limit, the current output will have a decrescent behavior (20~4

mA).

The values configured in these fields can not be beyond the sensor

measuring range. The minimum span value has to be observed as well

(see Table 01).

3. Line Noise Rejection: The transmitter incorporates a digital filter to

cancel the induced noise from the 50 or 60 Hz systems. For better

performance, select the line frequency used in your country.

4. Sensor Failure: establishes the transmitter output behavior (upscale or

down-scale) in the presence of a sensor fail.

5. Zero Correction: Allows for small sensor corrections.
6. Device Information: The Device Information box contains relevant data

concerning a particular transmitter. Please pass along this information

when contacting the technical assistance department.

7. Apply: Sends a new configuration to the transmitter.
8. Read Device: Brings to the screen the current transmitter parameters

configuration.

Note: The factory default configuration is (unless otherwise specified or

ordered):

Pt100 input, 0 to 100 ºC

60 Hz filtering and upscale (20 mA) output for sensor fail.

The transmitter must be powered in order to be configured. The TxConfig-USB

interface provides the necessary power. The TxConfig-RS232 interface,

however, requires an auxiliary supply to guarantee a reliable communication

with the computer.
An external 9 V battery can be used for this purpose (Fig. 1). An alternative is

to configure the transmitter while it is in operation; this way, the needed energy

is supplied by the current loop, as in Fig. 4.

Fig. 4 – TxConfig Interface connections – Loop powered

The TxConfig interfaces contain dedicated circuitry for proper

communication between transmitters and computer. Always make

use of the TxConfig interfaces for configuration purposes, otherwise

the transmitters may get damaged, voiding the warranty.

MECHANICAL INSTALLATION

The transmitter is intended for DIN rail mounting. Its drawing is presented in

Fig. 04.

Fig. 4 – Transmitter dimensions

ELECTRICAL CONNECTIONS

Figure below shows the transmitter connections to the sensor and power

supply. Terminals 1, 2 e 3 are used for sensor input. For 2-wire Pt100,

terminals 2 and 3 shall be connected together.

Fig. 5 – Transmitter wiring (Pt100)

Fig. 6 – Transmitter wiring (Thermocouple)

The LOAD represents the input shunt of an instrument measuring the 4-20

current loop.

Electrical Connections – 0-10 Vdc Input

For 0-10 Vdc input, the transmitter requires an internal hardware

configuration change. Please open the instrument case and change the

jumper shown in Fig. 07.

• Position 1-2 : 0-10 Vdc input
• Position 2-3 : all other input types

Fig. 7 – Jumper position for 0-10 Vdc input