beautypg.com

5 status words, 6 exception responses – error conditions – NOVUS N1020 User Manual

Page 2

background image

0030

dppo

PV decimal point position

Range: 0 to 3

0→X.XXX; 1→XX.XX; 2→XXX.X; 3→XXXX

0031

Sp.a1

Alarm 1 Setpoint.

Range: Between spll and spkl for non-differential

alarm or at spkl - spll for differential alarm.

0032

Sp.a2

Alarm 2 Setpoint. Range: same as in spa1.

0033~0034 Reserved

0035

Fva1

Alarm 1 Function. Range: 0 to 8

0→off; 1→lo; 2→ki; 3→dif;4→difl;

5→difk; 6→t..0n; 7→t..End; 8→err;

0036

Fva2

Alarm 2 Function. Range: same as in fua1.

0037~0038 Reserved

0039

Kya1

Alarm 1 Hysteresis. Range: 0 to 9999 (0.00 to

99.99%)

0040

Kya2

Alarm 2 Hysteresis. Range: same as in kya1.

0041~0042 Reserved

0043

type

PV input type

Range: 0 to 9. See operation manual.

0044

addr

Communication slave address.

Range: 1 to 247

0045

bavd

Communication Baud-Rate. Range: 0 to 7

0→1200;1→2400;2→4800;3→9600; 4→19200;

5→32400; 6→57600; 7→115200.

0046

avto

Control Mode. Range: 0→manual; 1→automatic.

0047

rvn

Enable control. Range: 0→no; 1→yes.

0048

act

Control action. Range: 0→direct; 1→reverse.

0049

atvn

Auto tune enable. Range: 0 to 5

0→FAST; 1→FULL; 2→SELF; 3→ RSLF;

4→TGHT.

0050

Bla1

Alarm 1 power-up inhibit. Range: 0→no; 1→yes.

0051

Bla2

Alarm 2 power-up inhibit. Range: same as in bla1.

0052~0053 Reserved

0054

Key

Key press remote action. Range: 0 to 9

1→ P; 2→

; 4→

; 8→ F

0055~0061 Reserved

0062

A1t1

Alarm 1 Time 1. Range: 0 to 6500s

Refer to Table 4 for more details.

0063

A1t2

Alarm 1 Time 2 (in seconds)

Range: same as in a1t1.

0064

A2t1

Alarm 2 Time 1 (in seconds)

Range: same as in a1t1.

0065

A2t2

Alarm 2 Time 2 (in seconds)

Range: same as in a1t1.

0066

sfst

Soft-Start time (in seconds)

Range: 0 to 9999

0067

vnit

Temperature unit. Range: 0 to 1

0→°C; 1→°F.

0068

Reserved

0069

TECO

Timer End Controller Off. Range: 0 to 1

0→ Disabled; 1→ Enable.

0070~0080 Reserved

0081

FLSH

Enables the top display blinking as a function of the

selected alarm. Range: 0 to 1

0→ Disabled; 1→ Enable.

0082

0uT1

Output 1 function. Range: 0 to 4

0→off; 1→Ctrl; 2→A1; 3→A2; 4→A1A2.

0083

0uT2

Output 2 function. Range: 0 to 4

0→off; 1→Ctrl; 2→A1; 3→A2; 4→A1A2.

0084~0085 Reserved

0086

Rstr

Restores original default calibration. Range: 0 to 1.

0→do not restore; 1→ restore calibration

0087

Reserved

Internal use

0088

Prot

Password protection level. Range: 1 to 5.

Check instruction manual for further details.

0089

PRTY

Serial communication parity. Range: 0 to 2.

0→no parity; 1→ even; 2→ odd;

1.5 STATUS WORDS

Register

Value Format

Status Word 1

bit 0 - Alarm 1 (0-inactive; 1-active)

bit 1 - Alarm 2 (0-inactive; 1-active)

bit 2 ~ 7 - Reserved

bit 8 - Hardware detection value

bit 9 - Hardware detection value

bit 10 ~15 - Reserved

Status Word 2

bit 0 - Automatic (0- manual; 1- automatic)

bit 1 - Run (0-stop; 1-run)

bit 2 - Control Action 1 (0-direct; 1 reverse)

bit 3 - Reserved

bit 4 - Auto-tune (0-no; 1-yes)

bit 5 - Alarm 1 power-up inhibit 1 (0-no; 1-yes)

bit 6 - Alarm 1 power-up inhibit 2 (0-no; 1-yes)

bit 7 - 8 - Reserved

bit 9 - Unit (0-°C; 1-°F)

bit 10 - Reserved

bit 11 - Output 1 status

bit 12 - Output 2 status

bit 13 - 14 - 15 - Reserved

Status Word 3

bit 0 - Very low PV conversion (0-no; 1-yes)

bit 1 - Negative conversion after calibration (0-no; 1-yes)

bit 2 - Very high PV conversion (0-no; 1-yes)

bit 3 - Exceeded linearization limit (0-no; 1-yes)

bit 4 - Very high Pt100 cable resistance (0-no; 1-yes)

bit 5 - Self zero conversion out of range (0-no; 1-yes)

bit 6 - Self span conversion out of range (0-no; 1-yes)

bit 7 ~ 15 - Reserved

Table 2 - Value of Status Words

Writing to an output bit is only possible if the output has no function assigned to it (the

output is configured to OFF in Alarm Cycle).

Coil Status

Output description

0

Output 1 Status 1 (I/O1)

1

Output 1 Status 2 (I/O2)

2

Output 1 Status 3 (I/O3)

3

Output 1 Status 4 (I/O4)

4

Output 1 Status 5 (I/O5)

1.6 EXCEPTION RESPONSES – ERROR CONDITIONS

The MODBUS RTU protocol checks the CRC in the data blocks received. Reception

errors are detected by the CRC, causing the controller to discard the packet, not

sending any reply to the master. After receiving an error-free packet, the controller

processes the packet and verifies whether the request is valid or not, sending back an

exception error code in case of an invalid request. Response frames containing error

codes have the most significant bit of the Modbus command set.
If a WRITE command sends an out-of-range value to a parameter, the controller will

clamp the value to the parameter range limits, replying with a value that reflects these

limits (maximum or minimum value allowed for the parameter).
The controller ignores broadcast READ commands; the controller processes only

broadcast WRITE commands.

Error Code

Error Description

01

Invalid Command or inexistent

02

Invalid Register Number or out of range

03

Invalid Register Quantity or out of range

Table 3 – Exception response error codes