Nor-Lake Capsule Pak Refrigeration Systems User Manual
Page 8
8
07/14 Rev. H 040086
geneRal inStallation inStRuCtionS
This section has the general instructions for installing the ceiling
mounted Refrigeration System. Before proceeding, also see the
following section on mounting "Remote Systems with Electric
Vaporizer", if applicable.
Note: Proper "temporary" interior support must be added during the
installation of the refrigeration.
Note: Due to the weight of these systems, it is highly recommended
that proper lifting equipment, such as a fork lift or scissor lift, be utilized
during installation. Also, be sure to allow for sufficient airflow around
the condenser. Model numbers ending with the letter "A" require
a minimum clearance of two feet for proper unit operation. Model
numbers ending with the letter "B" require a minimum of five inches
behind the unit and open to
the front for proper operation.
If multiple units are located
in the same area, be sure
they do not exhaust hot air
into one another. In addition
to allowing for proper airflow,
consideration should be
given to the final mounting
location of the refrigeration
system relative to the
customer location to avoid
any possible risk of noise
impacting the customer
experience.
Position the insulated
evaporator section of the
Refrigeration System over
the hole in the walk-in ceiling
section.
Align the tabs on the side of the insulated evaporator section with
the predrilled holes in the ceiling section. Before proceeding to the
next step, the evaporator cover should be removed. Look inside
the evaporator section and be sure the air divider in the ceiling section lines up with the black gasket divider in
the evaporator section. Some adjustment may be required by simply bending the ceiling section divider slightly
forward or backward. This will prevent any short cycling of discharge and return air.
Fasten the insulated evaporator section down to the ceiling using the provided drive screws, which can be
found attached to the side of the refrigeration system. CAUTION! This must be done to prevent the entire
refrigeration system from moving during operation.
Note: On smaller refrigeration systems, you may elect to install the system on the ceiling section while the section
is still on the floor.
CAUTION! Make sure to fasten down the system to the ceiling panel. The ceiling section and
the refrigeration system may then be erected together in the normal sequence of assembly as shown in the Kold
Locker™ Walk-in Installation Instructions. This method is not practical and should not be used with larger systems
of 100 series or above, such as a 100, 150 or 151 model.